PAT400 Series
83
Test Groups for Australian/New Zealand PAT Variants:
Test Group
Class
Description
Test Applied
Pass Limit
Test
Duration
Used in
AU-SC1
1
Standard Class 1
Earthed Equipment
Visual Inspection
Earth Continuity (200mA)
Insulation test at 500V
≤1Ω
≥1MΩ
5s
5s
PAT410
PAT420
PAT450
AU-SC1-
250V
1
Standard Class 1
Earthed Equipment
Visual Inspection
Earth Continuity (200mA)
Insulation test at 250V
≤1Ω
≥1MΩ
5s
5s
PAT410
PAT420
PAT450
AU-SC1-RCD
1
Standard Class 1
Earthed Equipment with
RCD Protection
Visual Inspection
RCD 30mA test
Earth Continuity (200mA)
Insulation test at 500V
≤1Ω
≥1MΩ
5s
5s
PAT410
PAT420
PAT450
AU-SC1-EB
1
Standard Class 1
Earthed Equipment
Earth Bond
Visual Inspection
Earth Bond at 10A
Insulation test at 500V
≤1Ω
≥1MΩ
5s
5s
PAT420
PAT450
AU-SC1-RUN
1
Standard Class 1
Earthed Equipment
Visual Inspection
Earth Continuity (200mA)
Insulation test at 500V
Differential Earth Leakage (230V)
≤1Ω
≥1MΩ
≤5mA
5s
5s
5s
PAT410
PAT420
PAT450
AU-SC2
2
Typical Class 2
Double Insulated
Visual Inspection
Insulation test at 500V
≥1MΩ
5s
PAT410
PAT420
PAT450
AU-SC2-
250V
2
Typical Class 2
Double Insulated
Visual Inspection
Insulation test at 250V
≥1MΩ
5s
PAT410
PAT420
PAT450
AU-SC2-RUN
2
Typical Class 2
Double Insulated
Visual Inspection
Insulation test at 500V
Differential Earth Leakage (230V)
≥1MΩ
≤1mA
5s
5s
PAT410
PAT420
PAT450
AU-EL1
EXT
230V Extension Leads
3 Core
Visual Inspection
Polarity
Earth Continuity (200mA)
Insulation test at 500V
≤1Ω
≥1MΩ
5s
5s
PAT410
PAT420
PAT450
AU-EL2
EXT
230V Extension Leads
2 Core
Visual Inspection
Polarity
Insulation test at 500V
≥1MΩ
5s
PAT410
PAT420
PAT450
AU-EL4
EXT
4 way 230V Extension
Leads
3 Core
200mA Continuity Test
Visual Inspection
Polarity
Earth Continuity (x4)
Insulation test at 500V
≤1Ω
≥1MΩ
5s
5s
PAT410
PAT420
PAT450
AU-RCD
1
Portable RCD 30mA
Visual Inspection
RCD 30mA test
PAT410
PAT420
PAT450
AU-RCD
FULL
1
Portable RCD (5 tests)
Visual Inspection
RCD full test sequence
PAT410
PAT420
PAT450