Insulation Testing
1. 

Turn the instrument ‘On‘ by selecting the M

range.

2. 

Connect the test probes to the isolated circuit under test. 

3.

Press and hold the push button; the display shows the insulation value.The
reading will remain displayed for a few seconds after the push button is
released. As an additional safety feature, instruments with 1000V range will
flash

symbol before performing a test. 

4. 

Release the push button before removing the test leads (to enable the 
instrument to discharge the circuit under test).  

5.

On completion switch to the ‘OFF’ position. Alternatively auto shut off
operates after  12 minutes of inactivity.

SPECIFICATION

Insulation

Test Voltage Accuracy:

-0% + 30% (over full operating temperature) 
into 0 to 1mA load

Measuring Range:

0,01M

- 999M

(Digital)

0,1M

(Analogue)

Short Cct. Current:

Less than 2mA

Accuracy (at 20°C):

± 3% ±2 digits up to 10M

± 5% ±2 digits up to 100M

± 30% up to 999M

Output Noise Voltage:

Typically 2V pk to pk at 20kHz (at 1mA load)

Hum Rejection:

<10% error with 100µA RMS (0,2M

to 

)

Continuity

Measuring Range:

0,01

- 99,9

Open Cct. Voltage:

5V ±1V

Accuracy (at 20°C):

0,01

- 9,99

±3% ± 2 digits (

I

SC

>200mA)

10

Ω − 

100

Ω 

± 5% ± 2 digits (

I

SC

>20mA) 

Lead res. comp:

0 to 9,99

Hum Rejection:

<3% error with 1V RMS (0,2

Ω 

to 50

)

Continuity Beeper:

On 

position, the beeper sounds at <5

Ω 

resistance

Environmental Conditions

Temperature Coefficient: <0,1% per °C
Temperature Range: 

Operating: 

-20°C to +40°C (full measurement range)

-20°C to +60°C (to 100 M

maximum)

Storage:

-25°C to +65°C 

Humidity:  

90% RH at 40°C max

General Specifications

Display:

3 digit L.C.D.  Maximum reading 999

Auto Shut off: 

Operates after 5 minutes of inactivity by the

instrument in Continuity position and 12 minutes in Insulation position. Beep
notes pre-empt auto shut off.  The instrument can be switched back on by
pressing the test button, or by selecting ‘OFF‘ and then the required position.

Default Live Circuit Warning (

BM221

;

BM222

BM223

and

BM227

)

When more than 25 V is applied to the terminals, the instruments default to a
voltmeter on all switch positions except ‘OFF’ and 

. In addition, the beeper

1000V

100

200

300

400

500

600

700

800

900

1000

1100

1200

1300

0,01M

0,1M

1,0M

10M

100M

Load

Terminal Voltage

1000 V Range

500 V Range

0.5M

250 V Range

0,2M

0,5M

1M

2M

5M

0,2M

0,5M

1M

2M

5M

10M

Minimum Indicated Value

Terminal Characteristics

Limiting Value 

Summary of Contents for BM220 Series

Page 1: ...to become inoperable The Voltage warning does not function if OFF or is selected During an insulation test connections must not be touched After insulation tests capacitive circuits must be allowed to...

Page 2: ...strument On by selecting the range 2 If required zero test lead resistance by firmly shorting both leads together wait for the reading to stabilise and press the test button Display of the symbol conf...

Page 3: ...Voltage 5V 1V Accuracy at 20 C 0 01 9 99 3 2 digits ISC 200mA 10 100 5 2 digits ISC 20mA Lead res comp 0 to 9 99 Hum Rejection 3 error with 1V RMS 0 2 to 50 Continuity Beeper On position the beeper s...

Page 4: ...batteries Fuse 500 mA F H B C 10 kA min 32mm x 6mm To check this fuse select M open circuit the test leads and press the test button until a reading is obtained Display of the fuse symbol or an error...

Page 5: ...roved Repair Companies A number of independent instrument repair companies have been authorised for repair work on most Megger Instruments using genuine Megger spare parts Consult the Appointed Distri...

Page 6: ...038 PO Box 9007 Valley Forge PA 19484 9007 Tel 1 610 676 8500 U S A Fax 1 610 676 8610 Megger SARL 29 All e de Villemomble 93340 Le Raincy Paris Tel 33 1 43 02 37 54 France Fax 33 1 43 02 16 24 This i...

Page 7: ...le confirme la mise z ro Nota La mise z ro des c bles est annul e chaque fois que l instrument est arr t ou que la fonction Arr t automatique est activ e 3 Brancher les sondes d essai sur le circuit i...

Page 8: ...3 c c non sp cifi D charge automatique Les circuits capacitifs sont automatiquement d charg s lorsque le bouton d essai est rel ch apr s un essai d isolement Alimentation lectrique 6 piles 1 5V type I...

Page 9: ...i jedem Ausschalten des Ger ts oder Aktivieren der automatische Abschaltfunktion wieder aufgehoben 3 Pr fspitzen an zu pr fenden Stromkreis anschlie en 4 Auf der Anzeige wird der Widerstand angezeigt...

Page 10: ...C keine Angaben Automatische Entladung Beim Loslassen der Pr ftaste nach einer Isolierpr fung werden die kapazitiven Stromkreise automatisch entladen Stromversorgung sechs 1 5 V Zellen nur IEC LR6 Leb...

Page 11: ...puesta a cero del conductor se cancela cada vez que se desconecta el instrumento o se activa desconexi n autom tica 3 Conecte las sondas de prueba al circuito aislado en prueba 4 El display muestra el...

Page 12: ...apacitivos son descargados autom ticament cuando se suelta el bot n de prueba despu s de una prueba de aislamiento Suministro de energ a 6 pilas de 1 5V de tipo IEC RL6 solamente Vida til de la bater...

Reviews: