Page 99
Speed Level Seres - Servce & Parts Manual
January 2019
Secton 8 - Troubleshootng - 3084RT Models
Operation
ID
Personality
Factory Setting
Explanation
6A
CHANGE
DEFAULTS
6A-1
Customer
5: XX84RT
Identifies Base Model
Must be set when GP400 is Replaced
6A-2
Model
5 = ANSI
6 = CE
Select from these choices only
6D
TILT SETUPS
6B-1
Calibrate Level?
Y = ENTER N = ESC
Follow instructions in Section 7- Level
Sensor Calibration
WARNING! Refer to Tilt Sensor Calibration instructions before attempting calibration
6B-2
Tilt Shutdown
0 = Never
Function shutdown tilted when platform
stowed
6B-3
Elevated Shutdown
1 = Lift & Drive
Function shutdown tilted when platform
elevated
6B-4
Axle Tilt
3.0 deg
Maximum deflection of axle before
elevated drive interlock
6C
HEIGHT SETUP
(CE OPTION
ONLY)
6C-1
Elevation @
13%
6C-2
Calibrate Height
Start Calibration
See Section 7 for calibration of Height
Sensor
6C-3
Minimum Lift
1.0 sec
Calibration setting - do not change
6C-4
Samples
0.10 sec
Calibration setting - do not change
6C-5
Tilt Correction
Disabled
Calibration setting - do not change
6C-6
Slow Down
10%
Calibration setting - do not change
6D
LOAD SETUPS
(CE OPTION
ONLY)
6D-1
Calibrate Load
Start Calibration
See Section 7 for calibration of CE
Overload System
6D-2
Faulty Load
100%
Calibration setting - do not change
6D-3
Dynamic Scale
95%
Calibration setting - do not change
6D-4
Delay Up
0.0 sec
Not Used
6D-5
Delay Down
0.0 sec
Not Used
6E
INTERLOCKS
6E-1
Trigger Only
10.0 sec
Enable bar held without operation before
interlock
6E-2
Trigger Wait
0.0 sec
Delay after enable bar pulled before
function enabled
6E-3
Function hold
0.2 sec
Function enabled after operator release
Delays
6E-4
Delays
-
Sub category, press ENTER to access
Sub Menu
6E-4a
Throttle Delay
0.0 sec
Delay before throttle enabled
6E-4b
Start Delay
10.0 sec
Interlocks start to protect start system
from overheat