22
MDS Orbit MCR-4G Technical Manual
MDS 05-6628A01, Rev. B
The following commands will configure the MCR-4G #2 for this scenario.
1.
%set
interfaces
interface
Wi
‐
Fi
physical
‐
interface
Wi
‐
Fi
wifi
‐
config
mode
station
station
‐
config
ap
myssid
enabled
true
2.
%set
interfaces
interface
myBridge
virtual
‐
type
bridge
3.
%set
interfaces
interface
myBridge
bridge
‐
settings
ports
port
ETH1
4.
%set
interfaces
interface
myBridge
bridge
‐
settings
ports
wifi
‐
station
interface
Wi
‐
Fi
5.
%set
interfaces
interface
myBridge
ipv4
address
192.168.1.22
prefix
‐
length
24
Example #3
Figure 13
shows the MCR-4G #2 device acts as a terminal server to provide connectivity to the serial-based
SCADA device via UDP.
Invisible place holder
Figure 13. Example 3: Unit Providing Connectivity to Serial-Based SCADA Device via UDP
The following commands will configure the MCR-4G #2 for this scenario.
1.
%set
interfaces
interface
Wi
‐
Fi
physical
‐
interface
Wi
‐
Fi
wifi
‐
config
mode
station
station
‐
config
ap
myssid
enabled
true
2.
%set
interfaces
interface
myBridge
virtual
‐
type
bridge
3.
%set
interfaces
interface
myBridge
bridge
‐
settings
ports
port
ETH1
4.
%set
interfaces
interface
myBridge
bridge
‐
settings
ports
wifi
‐
station
interface
Wi
‐
Fi
5.
%set
interfaces
interface
myBridge
ipv4
address
192.168.1.22
prefix
‐
length
24
6.
%set
services
serial
terminal
‐
server
server
COM1
mode
udp
port
30000
remote
address
192.168.1.11
port
30001
Ethernet
Ethernet
SCADA Device
serial
WiFi
SCADA
application
192.168.1.11
WiFi Access
Point
WiFi Access
Point
MCR-4G #2
192.168.1.22
MCR-4G #1
192.168.1.21