MX-2100/2104
Installation and Operation Manual
Chapter 2 Installation
Installation and Setup of MX-2100
2-15
Table 2-5. Module KCL.2, Internal Switch and Jumper Functions (Cont.)
Item Function
Switch SW2
1
2
3
4
(Switch is externally accessible from the panel)
Determines whether the Supervisory Port is used as a direct terminal or
for a SLIP connection:
ON - direct terminal
OFF - SLIP connection
SP Parameters: 9600 bps, 8,1,N
Currently not in use
Local basic software download:
OFF - normal function
ON - download software
For debugging purposes. Should always be set to OFF
Switch SW3
1
2
3
4
Sets MX-2100 as a Master. Should always be set to OFF
(Master only)
Database initialization. Should always be OFF
Determines whether MX-2100 requires a password when working with a
terminal:
ON - requires password
OFF - does not require password
Not in use. Should always be set to OFF
For MX-2104, the access to DIP Switch SW3 is through a hole in the upper cover.
You should load the default supervisory port password and communication
parameters (by setting sections 2 and 3 of DIP Switch SW3 to ON) if the current
parameters are not known, and the supervision terminal cannot communicate with
the MX-2100 enclosure. In such a case, first make sure the supervision terminal is
set for the correct parameters.
Installing the KCL.2 Module
Install the KCL.2 module in slot 5 of MX-2100.
Note
Note