IOMM AGR-1
AGR 070A through 100A
73
Menu #6:
Circuit 62 Pressures—The circuit #2 evaporator and condenser refrigerant pressure
readings are displayed under this menu. The calculated minimum and maximum condenser pressure
values are also shown.
Menu #7
: Circuit #l Temperatures—The circuit #I refrigerant temperatures are calculated from their
corresponding pressure sensors and displayed here. If the optional Sensors are not present, the line
item will flash “Open”.
Menu #8
: Circuit #2 Temperatures—The circuit #2 refrigerant temperatures are calculated from their
corresponding pressure sensors and displayed here. If the optional sensors are not present, the line
item will flash “Open”.
Menu#9:
Chiller Amps—Displays the present amp draw of the chiller expressed as a percentage of
the unit rated load amps under full load conditions (optional feature).
Menu #10:
Compressor Run Hours—The total run hours for each compressor is available under this
menu.
Menu #11:
Compressor Starts—The total number of starts for each compressor is available under this
menu.
Menu#12:
Air Temperature—Displays the current outdoor air temperature if the optional OAT sensor
is installed on the air cooled chiller and “Lcl” is selected from Menu 23. Also displayed here is the
air temperature received from a network if the “Rmt” OAT select option from Menu 23 is selected.
Control Menus
Menus 13 through 23 are the set point menus. All adjustable control parameters and set points, time
schedules, control options, and alarm thresholds are accessed through these menus.
CAUTION
Any changes to these parameters must be determined and implemented by qualified
personnel with a thorough understanding of how these parameters affect the operation of the
unit. Negligent or improper adjustment of these controls may result in damage to the unit or
personal injury.
Menu #13:
Control Mode—One of several automatic and manual operating modes may be selected
from within this menu. Typically, the selected control mode will be Automatic which will allow the
MicroTech controller to handle all compressor and condenser fan staging. Refrigerant circuit #2 may
be locked off while still allowing circuit #1 to stage automatically by selecting AutoCir#1 -Off#2 as
the operating mode. OffCirc#1 -Auto#2 allows the normal staging of refrigerant circuit #2 but circuit
#1 is locked off. Select Manual Staging if manual control is desired. In this operating mode, the
condenser fans are controlled by the MicroTech but the number of stages is determined manually via
the keypad. If manual staging is selected, the second item under this menu indicates the number of
active cooling stages. Use the INCR or DECR keys to increase or decrease the number of active
stages.
Menu#14:
Leaving Water Set Points—The leaving water set points, control band, maximum pull
down rate and water reset options are adjusted from this menu. The first menu item is The Active Set
Point ("Active Spt"). The current control temperature is displayed here. The Leaving Chilled Water
Set Point ("Lvg Evap") appears towards the top of this menu. These are the set points that will be
maintained for chillers if no reset options are in effect. The Active Control Set Point ("Active Spt")
will display the calculated chilled or heated water temperature to be maintained when one of the reset
options is enabled.
Summary of Contents for AGR 070AS
Page 20: ...20 AGR 070A through 100A IOMM AGR 1 Figure 9 Typical Field Wiring with Global UNT Controller...
Page 22: ...22 AGR 070A through 100A IOMM AGR 1 Figure 11 Standard Single Point Connection with FanTrol...
Page 24: ...24 AGR 070A through 100A IOMM AGR 1 Figure 13 Unit Control Schematic 2 compressor UNT...
Page 25: ...IOMM AGR 1 AGR 070A through 100A 25 Figure 14 Staging Schematic 2 compressor 4 stage UNT...
Page 26: ...26 AGR 070A through 100A IOMM AGR 1 Figure 15 Staging Schematic 2 compressor 6 stage UNT...
Page 27: ...IOMM AGR 1 AGR 070A through 100A 27 Figure 16 MicroTech Controller Schematic...
Page 28: ...28 AGR 070A through 100A IOMM AGR 1 Figure 17 Unit Control Schematic MicroTech...
Page 29: ...IOMM AGR 1 AGR 070A through 100A 29 Figure 18 Staging Schematic 4 stage MicroTech...
Page 30: ...30 AGR 070A through 100A IOMM AGR 1 Figure 19 Staging Schematic 6 stage MicroTech...
Page 31: ...IOMM AGR 1 AGR 070A through 100A 31 Figure 20 Unit Control Schematic 2 compressor MicroTech...
Page 32: ...32 AGR 070A through 100A IOMM AGR 1 Figure 21 UNT Instrument Layout See legend on page 34...
Page 35: ...IOMM AGR 1 AGR 070A through 100A 35 Figure 25 MicroTech Sensor Layout...
Page 99: ...IOMM AGR 1 AGR 070A through 100A 99 Notes...
Page 100: ...Post Office Box 2510 Staunton Virginia 24402 USA 800 432 1342 www mcquay com...