18
AGR 070A through 100A
IOMM AGR-1
Table 11, 60 Hz Single Point Power, Field Wiring Data
Wiring to Standard
Wiring to Optional
Power Block
Non-Fused Disconnect Switch
AGR
Unit
Size
Volts
Terminal
Amps
Connector Wire Range
(Copper Wire Only)
Terminal
Amps
Connector Wire Range
(Copper Wire Only)
208
335
# 4 - 400 MCM
400
250 - 500 MCM
230
335
# 4 - 400 MCM
400
250 - 500 MCM
380
335
# 4 - 400 MCM
250
#4 - 350 MCM
460
335
# 4 - 400 MCM
250
#4 - 350 MCM
070AS
070AM
575
335
# 4 - 400 MCM
150
#2 - 3/0
208
840
(2 qty.) 1/0 - 600 MCM
400
250 - 500 MCM
230
335
# 4 - 400 MCM
400
250 - 500 MCM
380
335
# 4 - 400 MCM
250
#4 - 350 MCM
460
335
# 4 - 400 MCM
250
#4 - 350 MCM
075AS
075AM
575
335
# 4 - 400 MCM
150
#2 - 3/0
208
840
(2 qty.) 1/0 - 600 MCM
400
250 - 500 MCM
230
840
(2 qty.) 1/0 - 600 MCM
400
250 - 500 MCM
380
335
# 4 - 400 MCM
250
#4 - 350 MCM
460
335
# 4 - 400 MCM
250
#4 - 350 MCM
080AS
080AM
575
335
# 4 - 400 MCM
250
#4 - 350 MCM
208
840
(2 qty.) 1/0 - 600 MCM
600
(2 qty.) 250 - 500 MCM
230
840
(2 qty.) 1/0 - 600 MCM
600
(2 qty.) 250 - 500 MCM
380
335
# 4 - 400 MCM
400
250 - 500 MCM
460
335
# 4 - 400 MCM
250
#4 - 350 MCM
085AS
085AM
575
335
# 4 - 400 MCM
250
#4 - 350 MCM
208
840
(2 qty.) 1/0 - 600 MCM
600
(2 qty.) 250 - 500 MCM
230
840
(2 qty.) 1/0 - 600 MCM
600
(2 qty.) 250 - 500 MCM
380
335
# 4 - 400 MCM
400
250 - 500 MCM
460
335
# 4 - 400 MCM
250
#4 - 350 MCM
090AS
090AM
575
335
# 4 - 400 MCM
250
#4 - 350 MCM
208
840
(2 qty.) 1/0 - 600 MCM
600
(2 qty.) 250 - 500 MCM
230
840
(2 qty.) 1/0 - 600 MCM
600
(2 qty.) 250 - 500 MCM
380
335
# 4 - 400 MCM
400
250 - 500 MCM
460
335
# 4 - 400 MCM
250
#4 - 350 MCM
095AS
095AM
575
335
# 4 - 400 MCM
250
#4 - 350 MCM
208
840
(2 qty.) 1/0 - 600 MCM
600
(2 qty.) 250 - 500 MCM
230
840
(2 qty.) 1/0 - 600 MCM
600
(2 qty.) 250 - 500 MCM
380
335
# 4 - 400 MCM
400
250 - 500 MCM
460
335
# 4 - 400 MCM
250
#4 - 350 MCM
100AS
100AM
575
335
# 4 - 400 MCM
250
#4 - 350 MCM
All Electrical Data notes are on page 19.
Summary of Contents for AGR 070AS
Page 20: ...20 AGR 070A through 100A IOMM AGR 1 Figure 9 Typical Field Wiring with Global UNT Controller...
Page 22: ...22 AGR 070A through 100A IOMM AGR 1 Figure 11 Standard Single Point Connection with FanTrol...
Page 24: ...24 AGR 070A through 100A IOMM AGR 1 Figure 13 Unit Control Schematic 2 compressor UNT...
Page 25: ...IOMM AGR 1 AGR 070A through 100A 25 Figure 14 Staging Schematic 2 compressor 4 stage UNT...
Page 26: ...26 AGR 070A through 100A IOMM AGR 1 Figure 15 Staging Schematic 2 compressor 6 stage UNT...
Page 27: ...IOMM AGR 1 AGR 070A through 100A 27 Figure 16 MicroTech Controller Schematic...
Page 28: ...28 AGR 070A through 100A IOMM AGR 1 Figure 17 Unit Control Schematic MicroTech...
Page 29: ...IOMM AGR 1 AGR 070A through 100A 29 Figure 18 Staging Schematic 4 stage MicroTech...
Page 30: ...30 AGR 070A through 100A IOMM AGR 1 Figure 19 Staging Schematic 6 stage MicroTech...
Page 31: ...IOMM AGR 1 AGR 070A through 100A 31 Figure 20 Unit Control Schematic 2 compressor MicroTech...
Page 32: ...32 AGR 070A through 100A IOMM AGR 1 Figure 21 UNT Instrument Layout See legend on page 34...
Page 35: ...IOMM AGR 1 AGR 070A through 100A 35 Figure 25 MicroTech Sensor Layout...
Page 99: ...IOMM AGR 1 AGR 070A through 100A 99 Notes...
Page 100: ...Post Office Box 2510 Staunton Virginia 24402 USA 800 432 1342 www mcquay com...