82
AGR 070A through 100A
IOMM AGR-1
Table 47, MENU 23 Misc Setup
Screen
Display
Factory Setpoint
Range
Unit Type= Air Cooled
1
2
Units = English
English
English - Metric
4
SpeedTrol = No
No
No - Yes
5
Power = 60 hz
60
60 - 50
6
Port A Baud=xxxx
9600
9600 - 2400 - 1200
Pre-Alarm=Blink
Blink
Blink - Open - Closed
Open
7
Closed
Alarm=Closed
Closed
Closed - Blink(N/O) - Blink(N/C)
Blink(N/O)
8
Blink(N/C)
OAT Select=None
None
None - Lcl - Rmt
Lcl
9
Rmt
10
LvgEvpAdj= 0.0 °F(°C)
-0.8 - 0.8 (-0.4 - 0.5)
11
EntEvpAdj= 0.0 °F(°C)
-0.8 - 0.8 (-0.4 - 0.5)
12
#1EvpAdj= 0.0psi (kPa)
(-13.8 - 13.8)
13
#2EvpAdj= 0.0psi (kPa)
(-13.8 - 13.8)
14
#1CndAdj= 0.0psi (kPa)
(-13.8 - 13.8)
15
#2CndAdj= 0.0psi (kPa)
(-13.8 - 13.8)
16
Refrigerant= R22
Not Changeable
17
Not Changeable
Table 48, MENU 24 #1 Curr Alarm
Screen
Display
1
Current Alarm
2
@ 0:00 0/00/00
3
Evap = x.x psi (kPa)
4
Cond = x.x psi (kPa)
5
SuctLine=xxx.x °F(°C)
6
LiquidLn=xxx.x °F(°C)
7
Evap Lvg=xxx.x °F(°C)
8
OAT=xx.xx°F(°C)
9
Capacity= xxx%
10
Fan Stage = x
Table 49, MENU 25 #2 Curr Alarm
Screen
Display
1
Current Alarm
2
@ 0:00 0/00/00
3
Evap = x.x psi (kPa)
4
Cond = x.x psi (kPa)
5
SuctLine=xxx.x °F(°C)
6
LiquidLn=xxx.x °F(°C)
7
Evap Lvg=xxx.x °F(°C)
8
OAT=xx.xx°F(°C)
9
Capacity= xxx%
10
Fan Stage = x
Table 50, MENU 26 #1 PrevAlarm
Screen
Display
1
1 Current Alarm
2
1 x:xx x/xx/xx
3
2 Current Alarm
4
2 x:xx x/xx/xx
5
3 Current Alarm
6
3 x:xx x/xx/xx
7
4 Current Alarm
8
4 x:xx x/xx/xx
9
5 Current Alarm
10
5 x:xx x/xx/xx
Table 51, MENU 27 #2 PrevAlarm
Screen
Display
1
1 Current Alarm
2
1 x:xx x/xx/xx
3
2 Current Alarm
4
2 x:xx x/xx/xx
5
3 Current Alarm
6
3 x:xx x/xx/xx
7
4 Current Alarm
8
4 x:xx x/xx/xx
9
5 Current Alarm
10
5 x:xx x/xx/xx
Summary of Contents for AGR 070AS
Page 20: ...20 AGR 070A through 100A IOMM AGR 1 Figure 9 Typical Field Wiring with Global UNT Controller...
Page 22: ...22 AGR 070A through 100A IOMM AGR 1 Figure 11 Standard Single Point Connection with FanTrol...
Page 24: ...24 AGR 070A through 100A IOMM AGR 1 Figure 13 Unit Control Schematic 2 compressor UNT...
Page 25: ...IOMM AGR 1 AGR 070A through 100A 25 Figure 14 Staging Schematic 2 compressor 4 stage UNT...
Page 26: ...26 AGR 070A through 100A IOMM AGR 1 Figure 15 Staging Schematic 2 compressor 6 stage UNT...
Page 27: ...IOMM AGR 1 AGR 070A through 100A 27 Figure 16 MicroTech Controller Schematic...
Page 28: ...28 AGR 070A through 100A IOMM AGR 1 Figure 17 Unit Control Schematic MicroTech...
Page 29: ...IOMM AGR 1 AGR 070A through 100A 29 Figure 18 Staging Schematic 4 stage MicroTech...
Page 30: ...30 AGR 070A through 100A IOMM AGR 1 Figure 19 Staging Schematic 6 stage MicroTech...
Page 31: ...IOMM AGR 1 AGR 070A through 100A 31 Figure 20 Unit Control Schematic 2 compressor MicroTech...
Page 32: ...32 AGR 070A through 100A IOMM AGR 1 Figure 21 UNT Instrument Layout See legend on page 34...
Page 35: ...IOMM AGR 1 AGR 070A through 100A 35 Figure 25 MicroTech Sensor Layout...
Page 99: ...IOMM AGR 1 AGR 070A through 100A 99 Notes...
Page 100: ...Post Office Box 2510 Staunton Virginia 24402 USA 800 432 1342 www mcquay com...