IOMM AGR-1
AGR 070A through 100A
11
CAUTION
Do not use an automotive grade antifreeze. Industrial grade glycols must be used.
Automotive antifreeze contains inhibitors which will cause plating on the copper tubes within
the chiller evaporator. The type and handling of glycol used must be consistent with local
codes.
Table 4, Ethylene Glycol
Freeze Point
%
E.G.
°F
°C
Cap.
kW
Flow
PD
10
26
-3
0.991
0.996
1.013
1.070
20
18
-8
0.982
0.992
1.040
1.129
30
7
-14
0.972
0.986
1.074
1.181
40
-7
-22
0.961
0.976
1.121
1.263
50
-28
-33
0.946
0.966
1.178
1.308
Table 5, Propylene Glycol
Freeze Point
%
P.G.
°F
°C
Cap.
kW
Flow
PD
10
26
-3
0.987
0.992
1.010
1.068
20
19
-7
0.975
0.985
1.028
1.147
30
9
-13
0.962
0.978
1.050
1.248
40
-5
-21
0.946
0.971
1.078
1.366
50
-27
-33
0.929
0.965
1.116
1.481
Table 6, Capacity and Power Derates
Fouling Factor
Chilled Water
Delta-T
0.0001 (0.0176)
0.00025 (0.044)
0.00075 (0.132)
0.00175 (0.308)
ALTITUDE
°F
°C
Cap.
Power
Cap.
Power
Cap.
Power
Cap.
Power
6
3.3
0.992
0.995
0.985
0.993
0.962
0.986
0.919
0.972
8
4.4
0.995
0.997
0.988
0.995
0.965
0.988
0.922
0.974
SEA
10
5.6
1.000
1.000
0.993
0.998
0.970
0.991
0.927
0.977
LEVEL
12
6.7
1.005
1.002
0.998
1.000
0.975
0.993
0.932
0.979
14
6.8
1.010
1.005
1.003
1.003
0.980
0.996
0.936
0.982
16
8.9
1.014
1.007
1.007
1.005
0.984
0.998
0.940
0.984
6
3.3
0.978
1.005
0.971
1.003
0.949
0.996
0.906
0.982
8
4.4
0.982
1.007
0.975
1.005
0.953
0.998
0.910
0.984
2000 feet
10
5.6
0.986
1.009
0.979
1.007
0.956
1.000
0.914
0.986
(610 m)
12
6.7
0.992
1.011
0.985
1.009
0.962
1.002
0.919
0.988
14
6.8
0.997
1.014
0.990
1.012
0.967
1.005
0.924
0.991
16
8.9
1.000
1.016
0.993
1.014
0.970
1.007
0.927
0.993
6
3.3
0.966
1.016
0.959
1.014
0.937
1.007
0.895
0.993
8
4.4
0.969
1.018
0.962
1.016
0.940
1.009
0.898
0.995
4000 feet
10
5.6
0.973
1.021
0.966
1.019
0.944
1.012
0.902
0.998
(1220 m)
12
6.7
0.978
1.025
0.971
1.023
0.949
1.016
0.906
1.002
14
6.8
0.982
1.027
0.975
1.025
0.953
1.018
0.910
1.004
16
8.9
0.986
1.028
0.979
1.026
0.956
1.019
0.914
1.005
6
3.3
0.953
1.025
0.946
1.023
0.924
1.016
0.883
1.002
8
4.4
0.955
1.028
0.948
1.026
0.926
1.019
0.885
1.005
6000 feet
10
5.6
0.959
1.031
0.952
1.029
0.930
1.022
0.889
1.008
(1830 m)
12
6.7
0.963
1.034
0.956
1.032
0.934
1.024
0.893
1.011
14
6.8
0.968
1.036
0.961
1.034
0.939
1.026
0.897
1.013
16
8.9
0.972
1.037
0.965
1.035
0.943
1.027
0.901
1.014
Summary of Contents for AGR 070AS
Page 20: ...20 AGR 070A through 100A IOMM AGR 1 Figure 9 Typical Field Wiring with Global UNT Controller...
Page 22: ...22 AGR 070A through 100A IOMM AGR 1 Figure 11 Standard Single Point Connection with FanTrol...
Page 24: ...24 AGR 070A through 100A IOMM AGR 1 Figure 13 Unit Control Schematic 2 compressor UNT...
Page 25: ...IOMM AGR 1 AGR 070A through 100A 25 Figure 14 Staging Schematic 2 compressor 4 stage UNT...
Page 26: ...26 AGR 070A through 100A IOMM AGR 1 Figure 15 Staging Schematic 2 compressor 6 stage UNT...
Page 27: ...IOMM AGR 1 AGR 070A through 100A 27 Figure 16 MicroTech Controller Schematic...
Page 28: ...28 AGR 070A through 100A IOMM AGR 1 Figure 17 Unit Control Schematic MicroTech...
Page 29: ...IOMM AGR 1 AGR 070A through 100A 29 Figure 18 Staging Schematic 4 stage MicroTech...
Page 30: ...30 AGR 070A through 100A IOMM AGR 1 Figure 19 Staging Schematic 6 stage MicroTech...
Page 31: ...IOMM AGR 1 AGR 070A through 100A 31 Figure 20 Unit Control Schematic 2 compressor MicroTech...
Page 32: ...32 AGR 070A through 100A IOMM AGR 1 Figure 21 UNT Instrument Layout See legend on page 34...
Page 35: ...IOMM AGR 1 AGR 070A through 100A 35 Figure 25 MicroTech Sensor Layout...
Page 99: ...IOMM AGR 1 AGR 070A through 100A 99 Notes...
Page 100: ...Post Office Box 2510 Staunton Virginia 24402 USA 800 432 1342 www mcquay com...