72
AGR 070A through 100A
IOMM AGR-1
Decr. - When changing the value of a menu item entry, pressing “DECR. -” shifts the menu item
display line to the next lower value or previous available selection.
Enter - Once a change has been made to a desired value, pressing “ENTER” locks in the new value.
Clear - Pressing “ALARMS” followed by “CLEAR” clears the current alarm. Also, when a change is
made to a menu item pressing “CLEAR” returns the display to the original value as long as “ENTER”
has not been pressed.
Note:
The cause of an alarm should always be determined and corrected before resetting the alarm
through the keypad.
Example of Keypad Operation -As an example of using the keypad key functions, consider
reprogramming the Leaving Evaporator Set Point from 44°F to 42°F. This consists of changing the
Menu Item 148 (Leaving Evaporator Set Point) entry from “44°F to 42°F”. Assume Menu #I (Unit
Status) is currently in the display. The following key sequence is followed.
1.
Press the “CATEGORY” group “CONTROL” key one time. This switches the display to Menu
#I13 (the first menu in the “CONTROL” category).
2.
Press the “MENU” group “NEXT” key once. This shifts the display to Menu Item 14A (Active
Set Point).
3.
Press the “ITEM” group “NEXT’ key once. This shifts the display to Menu Item 14B. (Leaving
Evaporator setpoint).
4.
Press the “ACTION” group ‘DEC -” key one time. This prompts the user to enter the password.
“E
NTER
” “E
N T E R
” “E
N T E R
” “E
N T E R
”
5.
After the “Password Verified” message, press the “ACTION” group “DEC -” key four times. This
changes the menu item entry to 42°F.
6.
Press the “ACTION” group “ENTER” key one time. This stores the new entry into the
MicroTech controller memory.
7.
Pressing the “CATEGORY” group “STATUS” key then shifts the display back to Menu #I.
Menu Descriptions
Status Menus
Menus 1 through 12 provide chiller operating information and display of sensor readings. The items
listed under these status menus are affected by the settings under the associated control menus and are
not directly adjusted via the keypad.
Menu #l:
Unit Status—The unit operating status is displayed as item 1 within this menu. The second
item is the number of seconds remaining in the unit interstage timer. The third item displays the user
chosen unit operation of chiller or Templifier (heat pump). Option chosen on Menu 23.
Menu #2:
Circuit #l Status—The current operating condition of refrigerant circuit #l is displayed
whenever this menu is selected. There is only one item displayed in this menu.
Menu #3
: Circuit #2 Status—The current operating condition of refrigerant circuit #2 is displayed
whenever this menu is selected. There is only one item displayed in this menu.
Menu #4:
Water Temperatures—The evaporator leaving water temperature is displayed under item #l
under this menu. Additional items under this menu display the evaporator entering water temperature
as well as the entering and leaving condenser temperatures if these optional sensors have been
installed on the unit.
Menu #5:
Circuit #l Pressures—The circuit #l evaporator and condenser refrigerant pressure readings
are displayed under this menu. The calculated minimum and maximum condenser pressure values are
also shown.
Summary of Contents for AGR 070AS
Page 20: ...20 AGR 070A through 100A IOMM AGR 1 Figure 9 Typical Field Wiring with Global UNT Controller...
Page 22: ...22 AGR 070A through 100A IOMM AGR 1 Figure 11 Standard Single Point Connection with FanTrol...
Page 24: ...24 AGR 070A through 100A IOMM AGR 1 Figure 13 Unit Control Schematic 2 compressor UNT...
Page 25: ...IOMM AGR 1 AGR 070A through 100A 25 Figure 14 Staging Schematic 2 compressor 4 stage UNT...
Page 26: ...26 AGR 070A through 100A IOMM AGR 1 Figure 15 Staging Schematic 2 compressor 6 stage UNT...
Page 27: ...IOMM AGR 1 AGR 070A through 100A 27 Figure 16 MicroTech Controller Schematic...
Page 28: ...28 AGR 070A through 100A IOMM AGR 1 Figure 17 Unit Control Schematic MicroTech...
Page 29: ...IOMM AGR 1 AGR 070A through 100A 29 Figure 18 Staging Schematic 4 stage MicroTech...
Page 30: ...30 AGR 070A through 100A IOMM AGR 1 Figure 19 Staging Schematic 6 stage MicroTech...
Page 31: ...IOMM AGR 1 AGR 070A through 100A 31 Figure 20 Unit Control Schematic 2 compressor MicroTech...
Page 32: ...32 AGR 070A through 100A IOMM AGR 1 Figure 21 UNT Instrument Layout See legend on page 34...
Page 35: ...IOMM AGR 1 AGR 070A through 100A 35 Figure 25 MicroTech Sensor Layout...
Page 99: ...IOMM AGR 1 AGR 070A through 100A 99 Notes...
Page 100: ...Post Office Box 2510 Staunton Virginia 24402 USA 800 432 1342 www mcquay com...