IOMM ACZ/AGZ-1
Table 47, MENU 20 Schedule
Screen
Display
Factory Setpoint
Range
1
Override= xx.xx hr
0.00 Hr
00:00 - 63.50
2
NMPSchedule= N/A
N/A
3
Sun 00:00-23:59
00:00 - 23:59
00:00 - 23:59
4
Mon 00:00-23:59
00:00 - 23:59
00:00 - 23:59
5
Tue 00:00-23:59
00:00 - 23:59
00:00 - 23:59
6
Wed 00:00-23:59
00:00 - 23:59
00:00 - 23:59
7
Thu 00:00-23:59
00:00 - 23:59
00:00 - 23:59
8
Fri 00:00-23:59
00:00 - 23:59
00:00 - 23:59
9
Sat 00:00-23:59
00:00 - 23:59
00:00 - 23:59
10
Hol 00:00-23:59
00:00 - 23:59
00:00 - 23:59
Table 48, MENU 21 Holiday Date
Screen
Display
Factory Setpoint
Range
1
#1 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
2
#1 Dur = 0 Day(s)
0
0 - 31
3
#2 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
4
#2 Dur = 0 Day(s)
0
0 - 31
5
#3 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
6
#3 Dur = 0 Day(s)
0
0 - 31
7
#4 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
8
#4 Dur = 0 Day(s)
0
0 - 31
9
#5 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
10
#5 Dur = 0 Day(s)
0
0 - 31
11
#6 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
12
#6 Dur = 0 Day(s)
0
0 - 31
13
#7 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
14
#7 Dur = 0 Day(s)
0
0 - 31
15
#8 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
16
#8 Dur = 0 Day(s)
0
0 - 31
17
#9 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
18
#9 Dur = 0 Day(s)
0
0 - 31
19
#10 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
20
#10 Dur = 0 Day(s)
0
0 - 31
21
#11 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
22
#11 Dur = 0 Day(s)
0
0 - 31
23
#12 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
24
#12 Dur = 0 Day(s)
0
0 - 31
25
#13 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
26
#13 Dur = 0 Day(s)
0
0 - 31
27
#14 Date = N/A 0
N/A 0
Jan - Dec 1 - 31
28
#14 Dur = 0 Day(s)
0
0 - 31
Table 49, MENU 22 Alarm Spts
Values for R-22 refrigerant, ( ) indicates Centigrade values
Screen
Display
Factory Setpoint
Range
1
FreezStat= xxpsi (kPa)
54 (372)
20 - 60 (138 - 414)
2
FreezH2O= xx.x °F (°C)
36.0 (2.3)
0.0 - 40.0 (-17.5 - 4.5)
3
FreezeTim= xxx sec
4
Hi Press = xxxpsi (kPa)
380 (2622)
280 - 426 (1932 - 2939)
Table 50, MENU 22 Alarm Spts
Values for 134a refrigerant, ( ) indicates Centigrade values
Screen
Display
Factory Setpoint
Range
1
FreezStat= xxpsi (kPa)
26 (179)
4 - 26 (27 - 179)
2
FreezH2O= xx.x °F (°C)
36.0 (2.3)
0.0 - 40.0 (-17.5 - 4.5)
3
FreezeTim= xxx sec
4
Hi Press = xxxpsi (kPa)
380 (2622)
280 - 426 (1932 - 2939)
Summary of Contents for ACZ 045A
Page 6: ...6 IOMM ACZ AGZ 1 Figure 3 Clearance Requirements...
Page 27: ...IOMM ACZ AGZ 1 27 Figure 12 AGZ AM Single point Connection with FanTrol...
Page 28: ...28 IOMM ACZ AGZ 1 Figure 13 AGZ AM Single point Connection with SpeedTrol...
Page 29: ...IOMM ACZ AGZ 1 29 Figure 14 AGZ AM Unit Control Schematic UNT...
Page 30: ...30 IOMM ACZ AGZ 1 Figure 15 AGZ AM Staging Schematic UNT...
Page 31: ...IOMM ACZ AGZ 1 31 Figure 16 AGZ AM MicroTech Controller Schematic...
Page 32: ...32 IOMM ACZ AGZ 1 Figure 17 AGZ AM Unit Control Schematic MicroTech...
Page 33: ...IOMM ACZ AGZ 1 33 Figure 18 AGZ AM Staging Schematic MicroTech...
Page 34: ...34 IOMM ACZ AGZ 1 Figure 19 ACZ Field Connection Diagram No Capacity Control...
Page 35: ...IOMM ACZ AGZ 1 35 Figure 20 ACZ Field Wiring Diagram Capacity Control Staging...
Page 104: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...