70
IOMM ACZ/AGZ-1
Pumpdown Control
The AGZ units have a one time pump down. If two compressors are operating on a refrigerant circuit
and the chiller is commanded to stop, the lag compressor on that circuit will stop and the lead
compressor will pump the circuit down. Pump down pressure depends on the chiller’s refrigerant type.
Certain alarm conditions will not permit chiller pumpdown. These alarm conditions are:
•
High Condenser Pressure
•
Bad Evap Pressure Sensor
•
Bad Phase Voltage
•
Volts Ratio Protect
•
Mechanical High Pressure
•
Compressor Motor Protect
Safety Systems
MicroTech continuously performs self diagnostic checks, monitoring all system temperatures,
pressures and safeties, and will automatically shut down a refrigerant circuit or the entire unit should a
fault occur. The cause of the shutdown, time and date of occurrence and conditions at the same time
of alarm will be retained in memory and can be displayed for the operator to review.
The MicroTech controller has several safety systems to safeguard against potential damage of the
chiller equipment. There are alarm and pre-alarm conditions. Alarm conditions cause the compressors
to shut off and/or lockout. Pre-alarm conditions cause the unit to stage down in capacity in an
attempt to avoid an alarm condition. For alarm conditions, the red “Alarm Status” light on the control
panel will be solid. For all pre-alarm conditions, the light will pulse at the rate of 0.5 seconds on, 4
seconds off. When an alarm of pre-alarm condition exists, the MicroTech display automatically
switches to the alarm menu to alert the user of the condition.
The MicroTech controller alarms can either be of the manual reset type or the auto reset type. Critical
alarm conditions such as High Condenser Pressure, Refrigerant Freeze Protection, and Low
Evaporator Pressure which protect against equipment damage are manual reset, which means they
lockout compressor operation and must be cleared at the MicroTech keypad before operation can
resume. Auto-clearing alarm conditions cause the compressors to shut off on the affected circuit until
the condition is corrected. When the condition is corrected, the chiller will resume normal operation
on that circuit, provided the anti-cycle timers have cleared and sufficient load exists. All pre-alarm
conditions are auto-clearing. After the controller stages down the unit on an alarm condition and the
potential alarm condition has been avoided, the alarm will clear y itself and the unit will resume normal
operation. If the alarm condition is not avoided, the alarm will be logged on the MicroTech display,
causing lockout of compressors. Thus, the alarm must be manually cleared.
When a McQuay Chiller with a MicroTech controller is used with the McQuay RMS (Remote
Monitoring and Sequencing) Panel, the user must note that alarm nomenclature varies. The RMS has
three possible categories of alarms: faults, problems, and warnings. The chiller alarm condition
corresponds with the RMS “fault” condition. Thus, there are system and circuit faults. Chiller pre-
alarm conditions correspond to the RMS “problem” designation. Reciprocating chillers do not have
warning alarms.
Summary of Contents for ACZ 045A
Page 6: ...6 IOMM ACZ AGZ 1 Figure 3 Clearance Requirements...
Page 27: ...IOMM ACZ AGZ 1 27 Figure 12 AGZ AM Single point Connection with FanTrol...
Page 28: ...28 IOMM ACZ AGZ 1 Figure 13 AGZ AM Single point Connection with SpeedTrol...
Page 29: ...IOMM ACZ AGZ 1 29 Figure 14 AGZ AM Unit Control Schematic UNT...
Page 30: ...30 IOMM ACZ AGZ 1 Figure 15 AGZ AM Staging Schematic UNT...
Page 31: ...IOMM ACZ AGZ 1 31 Figure 16 AGZ AM MicroTech Controller Schematic...
Page 32: ...32 IOMM ACZ AGZ 1 Figure 17 AGZ AM Unit Control Schematic MicroTech...
Page 33: ...IOMM ACZ AGZ 1 33 Figure 18 AGZ AM Staging Schematic MicroTech...
Page 34: ...34 IOMM ACZ AGZ 1 Figure 19 ACZ Field Connection Diagram No Capacity Control...
Page 35: ...IOMM ACZ AGZ 1 35 Figure 20 ACZ Field Wiring Diagram Capacity Control Staging...
Page 104: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...