IOMM ACZ/AGZ-1
23
Table 13, AGZ-AM, ACZ A, 60 Hz Single Point Power, Field Wiring Data
Wiring to Standard
Wiring to Optional
ACZ
AGZ-AM
Power Block
Non-Fused Disconnect Switch
Unit Size
Unit
Volts
Terminal
Connector Wire Range
Terminal
Connector Wire Range
Size
Amps
(Copper Wire Only)
Amps
(Copper Wire Only)
208
335
# 4 - 400 MCM
225
# 3 - 300 MCM
230
335
# 4 - 400 MCM
225
# 3 - 300 MCM
035AM
380
175
#12 - 2/0
100
#14 - 1/0
460
175
#12 - 2/0
100
#14 - 1/0
575
175
#12 - 2/0
100
#14 - 1/0
208
335
# 4 - 400 MCM
225
# 3 - 300 MCM
230
335
# 4 - 400 MCM
225
# 3 - 300 MCM
045A
040AM
380
175
#12 - 2/0
150
#4 - 4/0
460
175
#12 - 2/0
100
#14 - 1/0
575
175
#12 - 2/0
100
#14 - 1/0
208
335
# 4 - 400 MCM
225
# 3 - 300 MCM
230
335
# 4 - 400 MCM
225
# 3 - 300 MCM
050A
045AM
380
175
#12 - 2/0
150
#4 - 4/0
460
175
#12 - 2/0
100
#14 - 1/0
575
175
#12 - 2/0
100
#14 - 1/0
208
335
# 4 - 400 MCM
225
# 3 - 300 MCM
230
335
# 4 - 400 MCM
225
# 3 - 300 MCM
055A
050AM
380
335
# 4 - 400 MCM
150
#4 - 4/0
460
175
#12 - 2/0
150
#4 - 4/0
575
175
#12 - 2/0
150
#4 - 4/0
All Electrical Data notes are on page 23
Electrical Notes
Notes for “Electrical Data Single Point” Power:
1.
Unit wire size ampacity (MCA) is equal to 125% of the largest compressor-motor RLA plus 100%
of RLA of all other loads in the circuit including the control transformer.
2.
If the control transformer option is furnished, no separate 115V power is required.
3.
If a separate 115V power supply is used for the control circuit, then the wire sizing amps is 10
amps for all unit sizes.
4.
Recommended power lead wire sizes for 3 conductors per conduit are based on 100% conductor
ampacity in accordance with NEC. Voltage drop has not been included. Therefore, it is
recommended that power leads be kept short. All terminal block connections must be made with
copper (type THW) wire.
5.
“Recommended Fuse Sizes” are selected at approximately 150% to 175% of the largest
compressor RLA, plus 100% of all other loads in the circuit.
6.
“Maximum Fuse or HACR breaker size” is selected at approximately 225% of the largest
compressor RLA, plus 100% of all other loads in the circuit.
7.
The recommended power lead wire sizes are based on an ambient temperature of 86°F (30°C).
Ampacity correction factors must be applied for other ambient temperatures. Refer to the
National Electrical Code Handbook.
8.
Must be electrically grounded according to national and local electrical codes.
9.
MCA may vary slightly due to fan motor options such as SpeedTrol, TEFC.
Voltage Limitations:
Within
±
10 percent of nameplate rating.
Summary of Contents for ACZ 045A
Page 6: ...6 IOMM ACZ AGZ 1 Figure 3 Clearance Requirements...
Page 27: ...IOMM ACZ AGZ 1 27 Figure 12 AGZ AM Single point Connection with FanTrol...
Page 28: ...28 IOMM ACZ AGZ 1 Figure 13 AGZ AM Single point Connection with SpeedTrol...
Page 29: ...IOMM ACZ AGZ 1 29 Figure 14 AGZ AM Unit Control Schematic UNT...
Page 30: ...30 IOMM ACZ AGZ 1 Figure 15 AGZ AM Staging Schematic UNT...
Page 31: ...IOMM ACZ AGZ 1 31 Figure 16 AGZ AM MicroTech Controller Schematic...
Page 32: ...32 IOMM ACZ AGZ 1 Figure 17 AGZ AM Unit Control Schematic MicroTech...
Page 33: ...IOMM ACZ AGZ 1 33 Figure 18 AGZ AM Staging Schematic MicroTech...
Page 34: ...34 IOMM ACZ AGZ 1 Figure 19 ACZ Field Connection Diagram No Capacity Control...
Page 35: ...IOMM ACZ AGZ 1 35 Figure 20 ACZ Field Wiring Diagram Capacity Control Staging...
Page 104: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...