IOMM ACZ/AGZ-1
Glycol Solutions
The use of a glycol/water mixture in the CDE evaporator to prevent freezing will reduce system
capacity and efficiency and increase pressure drop. The system capacity, required glycol solution flow
rate, and pressure drop with glycol may be calculated using the following formulas and Table 4 and
Table 5.
1.
Capacity
–
Multiply the capacity based on water by the
Capacity
correction factor from or Table
4 and Table 5 to
2.
Flow
– Multiply the water evaporator flow by the
Flow
correction factor from and Table 4 or Table
5 determine the increased evaporator flow due to glycol
If the flow is unknown, it can be calculated from the following equation:
Factor
Correction
Flow
T
Delta
glycol
Capacity
Tons
(gpm)
Flow
Glycol
×
−
×
=
)
(
24
For Metric Applications
– Use the following equation for metric applications:
Factor
Correction
Flow
T
Delta
Capacity
k W
×
−
×
=
18
.
4
(l/s)
Flow
Glycol
3.
Pressure drop
-- Multiply the water pressure drop from Figure 7 by
Pressure Drop
correction
factor from Table 4 or Table 5 to obtain corrected glycol pressure drop. High concentrations of
propylene glycol at low temperatures may cause unacceptably high pressure drops.
4.
Power
-- Multiply the water system power by
Power
correction factor from Table 4 or Table 5.
Test coolant with a clean, accurate glycol solution hydrometer (similar to that found in service
stations) to determine the freezing point. Obtain percent glycol from the freezing point table below. It
is recommended that a minimum of 25% solution by weight be used for protection against corrosion.
CAUTION
Do not use an automotive grade antifreeze. Industrial grade glycols must be used.
Automotive antifreeze contains inhibitors which will cause plating on the copper tubes within
the chiller evaporator. The type and handling of glycol used must be consistent with local
codes.
Table 4, Ethylene Glycol Correction Factors
Freeze Point
%
E.G.
°F
°C
Capacity
Power
Flow
Pressure Drop
10
26
-3
0.991
0.996
1.013
1.070
20
18
-8
0.982
0.992
1.040
1.129
30
7
-14
0.972
0.986
1.074
1.181
40
-7
-22
0.961
0.976
1.121
1.263
50
-28
-33
0.946
0.966
1.178
1.308
Table 5, Propylene Glycol Correction Factors
Freeze Point
%
P.G.
°F
°C
Capacity
Power
Flow
Pressure Drop
10
26
-3
0.987
0.992
1.010
1.068
20
19
-7
0.975
0.985
1.028
1.147
30
9
-13
0.962
0.978
1.050
1.248
40
-5
-21
0.946
0.971
1.078
1.366
50
-27
-33
0.929
0.965
1.116
1.481
Note:
The procedure
does not specify the
type of glycol. Use
the derate factors
found in Table 4 for
corrections when
using ethylene glycol
and those in Table 5
for propylene glycol.
Summary of Contents for ACZ 045A
Page 6: ...6 IOMM ACZ AGZ 1 Figure 3 Clearance Requirements...
Page 27: ...IOMM ACZ AGZ 1 27 Figure 12 AGZ AM Single point Connection with FanTrol...
Page 28: ...28 IOMM ACZ AGZ 1 Figure 13 AGZ AM Single point Connection with SpeedTrol...
Page 29: ...IOMM ACZ AGZ 1 29 Figure 14 AGZ AM Unit Control Schematic UNT...
Page 30: ...30 IOMM ACZ AGZ 1 Figure 15 AGZ AM Staging Schematic UNT...
Page 31: ...IOMM ACZ AGZ 1 31 Figure 16 AGZ AM MicroTech Controller Schematic...
Page 32: ...32 IOMM ACZ AGZ 1 Figure 17 AGZ AM Unit Control Schematic MicroTech...
Page 33: ...IOMM ACZ AGZ 1 33 Figure 18 AGZ AM Staging Schematic MicroTech...
Page 34: ...34 IOMM ACZ AGZ 1 Figure 19 ACZ Field Connection Diagram No Capacity Control...
Page 35: ...IOMM ACZ AGZ 1 35 Figure 20 ACZ Field Wiring Diagram Capacity Control Staging...
Page 104: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...