48
IOMM ACZ/AGZ-1
Chilled Water Flow Switch
The chilled water flow switch is connected to field wiring terminals #142 and #143 on TB-7. When the
chilled water pump is enabled, the Global UNT controller checks for proof-of-flow through the flow
switch digital input.
Digital Outputs
The digital outputs are controlled by the Global UNT controller. The outputs are double pole double
throw plug-in type relays, with a 24Vac holding coil and 120Vac - 7.0 amp rated contacts. These relays
are field replaceable. Only one contact is used per relay. The contact that is used can be normally
open or normal closed and is dependent on the relay function.
External Alarm Annunciator Circuitry
An audible alarm can be connected to the Alarm Output terminals #19 and #28 of TB-3 of the control
panel and is highly recommended to make certain the operator is alerted to any alarm condition. This
output can also be used to alert a building automation system by paralleling a 24Vac control relay with
the alarm light. This circuit is a 24Vac 1.8 amp maximum load output. The alarm output will be
activated when an alarm condition occurs. Refer to the unit schematic.
Note:
The alarm signal is not active during a power failure and will not provide a “Loss of
Power” alarm.
PC Connection
The Global UNT controller can be connected to an IBM or IBM compatible computer for setpoint
changes and downloading of different software’s. A Global UNT Interface Kit is available from your
local McQuay Sales Representative.
Software Identification
Control software is factory installed and tested in each panel prior to shipment. The software is
identified by a program code which is printed on the a small label attached to the controller.
Controller Inputs /Outputs
Analog Inputs
Analog inputs are used to read the various temperatures and pressures on the chiller as well as any
customer supplied reset signals. The regulated 5Vdc power supply provides correct operating voltage
for the pressure transducers. This 5Vdc supply cannot be used for other inputs.
Table 17, Analog Inputs
Input
Description
Location
Range
AI-1
Leaving Chilled Water Temp
Leaving Chw nozzle
0 to 120°F(0 - 49°C)
AI-2
Circuit #1 Evap Pressure
Circuit #1 Suction Line
0 to 150 psi (0 - 1034kPa)
AI-3
Optional Reset input
TB-7 #134 and #135
0/2 to 10VDC / temp sensor
AI-4
Leaving Water Temp Setpoint Dial
Control Panel
10 to 60°F ( -12 to 15° C)
AI-5
Circuit #2 Evap Pressure
Circuit #2 Suction Line
0 to 150 psi (0 - 1034kPa)
AI-6
Control Band Setpoint Dial
Control Panel
0 to 10°F (-17 to -12°C)
Summary of Contents for ACZ 045A
Page 6: ...6 IOMM ACZ AGZ 1 Figure 3 Clearance Requirements...
Page 27: ...IOMM ACZ AGZ 1 27 Figure 12 AGZ AM Single point Connection with FanTrol...
Page 28: ...28 IOMM ACZ AGZ 1 Figure 13 AGZ AM Single point Connection with SpeedTrol...
Page 29: ...IOMM ACZ AGZ 1 29 Figure 14 AGZ AM Unit Control Schematic UNT...
Page 30: ...30 IOMM ACZ AGZ 1 Figure 15 AGZ AM Staging Schematic UNT...
Page 31: ...IOMM ACZ AGZ 1 31 Figure 16 AGZ AM MicroTech Controller Schematic...
Page 32: ...32 IOMM ACZ AGZ 1 Figure 17 AGZ AM Unit Control Schematic MicroTech...
Page 33: ...IOMM ACZ AGZ 1 33 Figure 18 AGZ AM Staging Schematic MicroTech...
Page 34: ...34 IOMM ACZ AGZ 1 Figure 19 ACZ Field Connection Diagram No Capacity Control...
Page 35: ...IOMM ACZ AGZ 1 35 Figure 20 ACZ Field Wiring Diagram Capacity Control Staging...
Page 104: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...