IOMM ACZ/AGZ-1
3. The charge can be added at any load condition between 25-100% load per circuit but at least twoF
fans should be operating per refrigerant circuit if possible. The suction superheat should be in the
6
°
F-12
°
F (3.3
°
C-6.6
°
C) range.
4. Add sufficient charge to clear the liquid line sightglass and until all flashing stops in the sightglass.
Add an extra 15-20 lbs. of reserve to fill the subcooler if the compressor is operating at 50-100%
load.
5. Check the unit subcooling value by reading the liquid line pressure and temperature at the liquid
line near the filter-drier. The subcooling values should be between 6 degrees F-20 degrees F (6.6
degrees C-11.1 degrees C). The subcooling values will be highest at 75-100% load, approximately 12
degrees F-20 degrees F (6.6 degrees C-11.1 degrees C) and lowest at 50% load, approximately 6
degrees F-12 degrees F (3.3 degrees C-6.6 degrees C).
6. With outdoor temperatures above 60
°
F (15.6
°
C) all condenser fans should be operating and the
liquid line temperature should be within 5
°
F-10
°
F (2.8
°
C-5.6
°
C) of the outdoor air temperature. At
25-50% load the liquid line temperature should be within 5
°
F (2.8
°
C) of outdoor air temperature with
all fans on. At 75-100% load the liquid line temperature should be within 10
°
F (5.6
°
C) of outdoor air
temperature with all fans on.
7. Overcharging of refrigerant will raise the compressor discharge pressure due to filling of the
condenser tubes with excess refrigerant.
Summary of Contents for ACZ 045A
Page 6: ...6 IOMM ACZ AGZ 1 Figure 3 Clearance Requirements...
Page 27: ...IOMM ACZ AGZ 1 27 Figure 12 AGZ AM Single point Connection with FanTrol...
Page 28: ...28 IOMM ACZ AGZ 1 Figure 13 AGZ AM Single point Connection with SpeedTrol...
Page 29: ...IOMM ACZ AGZ 1 29 Figure 14 AGZ AM Unit Control Schematic UNT...
Page 30: ...30 IOMM ACZ AGZ 1 Figure 15 AGZ AM Staging Schematic UNT...
Page 31: ...IOMM ACZ AGZ 1 31 Figure 16 AGZ AM MicroTech Controller Schematic...
Page 32: ...32 IOMM ACZ AGZ 1 Figure 17 AGZ AM Unit Control Schematic MicroTech...
Page 33: ...IOMM ACZ AGZ 1 33 Figure 18 AGZ AM Staging Schematic MicroTech...
Page 34: ...34 IOMM ACZ AGZ 1 Figure 19 ACZ Field Connection Diagram No Capacity Control...
Page 35: ...IOMM ACZ AGZ 1 35 Figure 20 ACZ Field Wiring Diagram Capacity Control Staging...
Page 104: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...