9
Controllo per i-HPV5
Chillers and Inverter Air/Water heat pumps with axial fan
4.2
MENU
The items controlled by the main menu are listed below. Some of this are only visible to the installer, who must access to the PSS menu to enter
the password and enable higher privilege access.
MENU
LABEL
LEVEL
OTHER CONDITIONS
Setpoint
Set
User
Not accessible if connected at Hi-T2V415
Password
PSS
User
---
Alarms
Err
User
Only if active alarms
Probes
tP
Installer
---
Digital inputs
Id
Installer
---
Parameters
Par
Installer
---
Hours of oper
-
ation
oHr
Installer
---
Alarm log
Hist
Installer
Only if the log contains data
Firmware
version
Fir
Installer
---
USB
USb
Installer
Only with USB key with update files is present
CAUTION: All operations with INSTALLER visibility must be carried out by QUALIFIED PERSONNEL.
4.3 SETPOINT MENU [
Set
]
In this menu, it is possible to display and modify the various set-points.
Set
DESCRIPTION
DEFAULT
RANGE
UNIT
Coo
First summer setpoint
7.0
5 ÷ Coo2
°C
Hea
First winter setpoint
45.0
Hea2 ÷ 60
°C
*San
Sanitary setpoint
48.0
25 ÷ 60
°C
*San2
Second sanitary setpoin
48.0
25 ÷ 60
°C
Coo2
Second Summer setpoint
18.0
Coo ÷ 25
°C
Hea2
Second Winter setpoint
35.0
25 ÷ Hea
°C
(*) If sanitary function is enabled, see par. 12.
4.4 PASSWORD MENU [PSS]
Enter the password for the desired access level. Confirming the value with the PRG key automatically activates the access level and the menu
items enabled by that level will appear. Once you have exited the menus completely, the password privilege is lost and must be entered again.
4.5 ALARMS MENU [
Err
]
This menu allows you to see all active alarms, if any . For more details see par. 23.
4.6 PROBES MENU [
tP
]
Entering with the installer password, the values of the present temperature and pressure sensors can be read in this menu.
tP
DESCRIPTION
UNIT
t01
Water inlet temperature
°C
t02
Water outlet temperature
°C
t03
Compressor suction temperature
°C
t04
Compressor discharge temperature 1
°C
t05
Outside air temperature
°C
t06
Compressor discharge temperature 2
°C
t08
System remote probe temperature / sanitary (if enabled)
°C
t09
Low pressure
bar
t10
High pressure
bar
The number of visible probes depends on the presence or absence of expansion modules.
Particular situations:
Err: probe faulty
--- = probe not used (no function associated to that probe)
Summary of Contents for i-HPV5H 0140
Page 32: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 32...
Page 33: ...33 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...
Page 34: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 34...
Page 35: ...35 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...