29
Controllo per i-HPV5
Chillers and Inverter Air/Water heat pumps with axial fan
Alarm code
DESCRIPTION
Block
E801
Inverter communication timeout
Compressor
E851
Inverter hardware problem
Compressor
E861
Motor current too high
Compressor
E871
High inverter heatsink temperature
Compressor
E881
Supply voltage out of limits (DC bus)
Compressor
E891
Compressor not connected
Compressor
E901
Wrong compressor model
Compressor
E911
Overload protection
Compressor
E921
PFC/POE overcurrent
Compressor
E931
Internal commhunication error
Compressor
E941
PFC fault
Compressor
E951
Heatsink and/or ambient temperature sensor fault
Compressor
E961
Abnormal condition
Compressor
E971
Errore EEPROM
Compressor
(*) if DS accessory is present
25. MODBUS VARIABLES
The control has the following modbus configuration by default:
•
Baud rate: 9600
•
Parity: EVEN
•
Data bit: 8
•
Stop bit: 1
• Device ID: 1
To configure the Modbus communication according to your requirements, you must modify the following parameters:
Parameter
VALUE
Function
H124
0
Baud rate 4800 bit/s
1
Baud rate 9600 bit/s
2
Baud rate 19200 bit/s
3
Baud rate 38400 bit/s
H125
0
Parity NONE and stop bit 2
1
Parity ODD and stop bit 1
2
Parity EVEN and stop bit 1
3
Parity NONE and stop bit 1
H126
1 ÷ 120
Serial address (Device ID)
The following table lists the Modbus registers of the control:
Register
Format
Bit
R/W
Range
Name
Description
Note
1
INT
-
R
-
Data version
Firmaware version
2
INT
-
R
-
Firmware release
3
BYTE (H)
-
R
-
Firmware sub-release
BYTE (L)
-
R
-
Firmware creation day
4
BYTE (H)
-
R
-
Firmaware creation month
BYTE (L)
-
R
-
Firmware creation year
10
BOOL
0
R
-
Digital inputs
ID1 (flow swich)
1
ID 2
If active
2
ID 3 (on/off)
Active by default
80 ÷ 95
ASCII
-
R
-
Serial number
Serial number
200
INT
0
R/W
-
Machine settings
Stand by
Writing non-permissible
values to this address
can lead to unexpected
operation, so stick to the
only values permitted for
writing (those above).
1
R/W
Cooling
2
R/W
Heating
5
R/W
C *Sanitary
6
R/W
H *Sanitary
-1
W
Defrost Manual
1089
INT
-
R/W
1 ÷ 200
Serial address
Modbus serial ID
Summary of Contents for i-HPV5H 0140
Page 32: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 32...
Page 33: ...33 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...
Page 34: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 34...
Page 35: ...35 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...