Controllo per i-HPV5
Chillers and Inverter Air/Water heat pumps with axial fan
20
•
r23 = 1 for boiler use on system only (priority of resistor intervention);
•
r23 = 2 for boiler use only in DHW mode (priority intervention of the heaters);
•
r23 = 3 for boiler use in DHW and on system (priority intervention of resistors);
•
r23 = 4 for boiler use only in system mode with priority;
•
r23 = 5 for boiler use only in DHW mode with priority;
•
r23 = 6 for boiler use in DHW mode and on system with priority;
Define the boiler equipment by setting parameter r32:
•
r32 = 0 for boiler without circulator with thermoregulation charged to the heat pump;
•
r32 = 1 for boiler with autonomous circulator with thermoregulation charged to the heat pump;
•
r32 = 2 for boiler without circulator with autonomous thermoregulation;
•
r32 = 3 for boiler equipped with circulator with autonomous thermoregulation.
Parameter
VALUE
Function
H88
29
Boiler enabling
r10
1
Enabling in system integration
r12
10 (default)
System integration activation delay (in minutes)
r15
1
Enabling of sanitary integration
r16
10 (default)
DHW integration activation delay (in minutes)
r23
1 ÷ 6
Type of boiler use
r32
1 ÷ 3
Boiler equipment
21.7
LOGIC OF INTEGRATION HEATERS AND/OR BOILER IN JOINT OPERATION OR IN SUB
-
STITUTION OF THE HEAT PUMP COMPRESSOR
The auxiliary parts that can be used for joint or for operation in substitution are:
•
boiler
•
system integration resistor
•
domestic hot water integration resistor
The parameters to be considered for adjusting this operating logic are:
•
r22 = set for joint operation with heat pump priority
•
r28 = set for joint operation with priority of auxiliary units
•
r08 = set for replacement operation
Considering the heating and/or DHW operating modes, there are 4 operating areas:
LOGIC OF INTEGRATION
r22
Heat pump + Boiler/Heater
JOINT OPERATION I ZONE
Heat pump/Heater
JOINT OPERATION II ZONE
Boiler/Heater
OPERATION IN SUBSTITUTION
Heat pump
STANDARD WORKING
r28
r08
Outside
temp.
If it is necessary to change the values of the parameters, the formula r22 ≥ r28 ≥ r08 must be followed.
Setting r22 = r28 it is possible to eliminate the zone relative to joint operation 1st band; by setting r28 = r08 it is possible to eliminate the zone
relative to joint operation 2nd band; by setting r22 = r28 = r08 it is possible to eliminate both bands relative to joint operation.
The intervention priorities of the auxiliary heaters are defined by parameters r14, r20, r23, r24 (as described above).
Summary of Contents for i-HPV5H 0140
Page 32: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 32...
Page 33: ...33 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...
Page 34: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 34...
Page 35: ...35 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...