11
Controllo per i-HPV5
Chillers and Inverter Air/Water heat pumps with axial fan
4. Power up the unit, setting the main switch to the ON position;
5. Access the firmware update menu and start the procedure through the following sequence: PRG -> PSS -> PRG -> (enter installer password)
-> PRG -> USB -> UPPA -> PRG;
6. A countdown advances on the display, at the end of the procedure the word "boot" appears and the 4 LEDs light up in sequence;
7. Remove the drive from the USB port;
8. Switch the unit on by turning the main switch to the ON position.
5. SYSTEM RESOURCES
The inputs and outputs (I/O) that can be set to activate the control functions are listed below. To configure the I/O, use the installer password to
access the configuration parameters: PRG -> PSS -> PRG -> (enter installer password) -> PRG ->
PAr
-> PRG ->
CnF
.
Resource
Parameter
Terminal block
Factory configuration
Description
Default
value
Function
ST8
H18
XC-12.1
XC-12.2
0
Not set
Analogue input configurable with an NTC-10kΏ
probe at 25°C β 3435
ST11
H22
XC-10.1 (GND)
XC-10.2 (+)
XC-11.2 (5V)
0
Voltage input
0-10 Vdc input (XC-10.1/2)
Ratiometric / PWM input
DI2
H46
XC-2.1
XC-2.2
0
Remote summer/winter mode
change
Voltage free digital input
To activate the function see par. 13.2
DI3
H47
XC-1.1
XC-1.2
2
Remote on/off
Voltage free digital input. Active function by default
DO7
H85
XP-10.1 (N)
XP-10.2 (fase)
6
HDW valve control
Voltage output 230Vac, 50Hz, 2A (AC1)
Modbus
RTU RS485
--
XC-1.1 (GND)
XC-2.1 (R-)
XC-2.2 (R+)
--
--
Factory enabled with CM accessory
For a detailed description of the terminal block, please refer to the user/installer manual.
6.
EDITING DYNAMIC SET-POINT
The regulation control allows you to modify the set-point by adding an offset value depending on the outside air temperature. To use this func
-
tion, modify the values of the regulation parameters, from b08 to b14, following the information in this paragraph.PRG -> PSS -> PRG -> (enter
installer password) -> PRG ->
PAr
-> PRG ->
rE
Parameters of regulator:
•
b08 = 1
to enable the dynamic set-point /
b08 = 0
to disable the dynamic set-point (default)
•
b09
= maximum cooling offset
•
b10
= maximum heating offset
•
b11
= Cooling outdoor temperature setting
•
b12
= Heating outdoor temperature setting
•
b13
= Cooling temperature delta
•
b14
= Heating temperature delta
Edit the setpoint depending on the outdoor temperature:
HEATING
COOLING
Set temp. ext
b12
b10
b14
Delta <0
Delta >0
Temp.
ext
Temp.
set
O
ff
set >0
Hea
Set temp. ext
b11
Temp.
set
O
ff
set <0
Coo
b13
Delta <0
Delta >0
Temp.
ext
SETPOINT DINAMICO - RAFFRESCAMENTO
b09
EXAMPLE: consider that we want to obtain the following conditions in heating mode:
• set-point of 28°C with external temperature of 18°C
• set-point of 45°C with external temperature of 2°C
Set Hea = 28 e b08 = 1, while the other parameters will be calculated as follows:
•
b10 = 45 – 28 = 17
•
b12 = 18
Summary of Contents for i-HPV5H 0140
Page 32: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 32...
Page 33: ...33 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...
Page 34: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 34...
Page 35: ...35 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...