23
Controllo per i-HPV5
Chillers and Inverter Air/Water heat pumps with axial fan
TABLE 3. JOINT OPERATION, BRACKET 2
INTERVENTION ORDER
STATUS
OPERATION
r10
r15
r12
r16
r23
r24
1) Boiler
2) After r12 minutes, heat pump
3) After further r12 minutes, plant inte
-
gration heater
HEAT /
HEAT+SAN
HEAT
1
0/1/2
Set the
minutes
/
4/6
1/3
1) Plant integration heater
2) After r12 minutes, heat pump
HEAT /
HEAT+SAN
HEAT
1
0/1/2
Set the
minutes
/
0/2/5
1/3
1) Boiler
2) After r16 minutes, heat pump
HEAT+SAN
SANITARY
0/1
0/1/2
/
Set the
minutes
2/3/5/6
0/1
1) Boiler
2) After r16 minutes, DHW integration
heater
3) After furher r16 minutes, heat pump
HEAT+SAN
SANITARY
0/1
1
/
Set the
minutes
2/3
2/3
1) Boiler
2) After r16 minutes, heat pump
3) After further r16 minutes, DHW inte
-
gration heater
HEAT+SAN
SANITARY
0/1
1
/
Set the
minutes
5/6
2/3
1) DHW intetgration heater
2) After r16 minutes, heat pump
HEAT+SAN
SANITARY
0/1
1
/
Set the
minutes
0/1/4
2/3
1) Boiler
2) After r12 minutes, heat pump
HEAT /
HEAT+SAN
HEAT / SANITARY
1
1
Set the
minutes
Set the
minutes
3/6
0
1) Boiler
2) After r12 minutes, plant/DHW inte
-
gration heater
3) After further r12 minutes, heat pump
HEAT /
HEAT+SAN
HEAT / SANITARY
1
1
Set the
minutes
Set the
minutes
3
3
1) Boiler
2) After r12 minutes, heat pump
3) After further r12 minutes, plant/DHW
integration heater
HEAT /
HEAT+SAN
HEAT / SANITARY
1
1
Set the
minutes
Set the
minutes
6
3
1) Plant/DHW integration heater
2) After r12 minutes, heat pump
HEAT /
HEAT+SAN
HEAT / SANITARY
1
1
Set the
minutes
Set the
minutes
0
3
TABLE 4. OPERATION IN SUBSTITUTION
INTERVENTION ORDER
STATUS
OPERATION
r10
r15
r12
r16
r23
r24
1) Boiler
2) After r12 minutes, Plant integration
heater
HEAT /
HEAT+SAN
HEAT
0/1
0/1/2
Set the
minutes
/
4/6
1/3
1) Plant integration heater
2) After r12 minutes, boiler
HEAT /
HEAT+SAN
HEAT
0/1
0/1/2
Set the
minutes
/
1/3
1/3
1) Boiler
2) After r12 minutes, DHW integration
heater
HEAT+SAN
SANITARY
0/1
0/1/2
/
Set the
minutes
5/6
2/3
1) DHW integration heater
2) After r12 minutes, boiler
HEAT+SAN
SANITARY
0/1
0/1/2
/
Set the
minutes
2/3
2/3
1) Boiler
2) After r12 minutes, Plant/DHW inte
-
gration heater
HEAT /
HEAT+SAN
HEAT/SANITARY
0/1
0/1/2
Set the
minutes
Set the
minutes
6
3
1) Plant/DHW integration heater
2) After r12 minutes, boiler
HEAT /
HEAT+SAN
HEAT/SANITARY
0/1
0/1/2
Set the
minutes
Set the
minutes
3
3
1) Boiler
HEAT /
HEAT+SAN
HEAT
0/1
0/1/2
Set the
minutes
/
1/3/4/6
0/2
1) Plant integration heater
HEAT /
HEAT+SAN
HEAT
0/1
0/1/2
Set the
minutes
/
0/2/5
1/3
1) Boiler
HEAT+SAN
SANITARY
0/1
0/1/2
/
Set the
minutes
2/3/5/6
0/1
1) DHW integration heater
HEAT+SAN
SANITARY
0/1
0/1/2
/
Set the
minutes
0/1/4
2/3
1) Boiler
HEAT /
HEAT+SAN
HEAT / SANITARY
0/1
0/1/2
Set the
minutes
Set the
minutes
3/6
0
1) Plant/DHW integration heater
HEAT /
HEAT+SAN
HEAT / SANITARY
0/1
0/1/2
Set the
minutes
Set the
minutes
0
3
Table 5 shows the settings to be configured to enable integrations in COOL + SAN mode. In this case, the only integration that can be enabled is
Summary of Contents for i-HPV5H 0140
Page 32: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 32...
Page 33: ...33 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...
Page 34: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 34...
Page 35: ...35 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...