Controllo per i-HPV5
Chillers and Inverter Air/Water heat pumps with axial fan
26
Parame-
ter
Description
Unit Default
Range
Visibility
Allowed configurations:
Description
Notes
b11
Cooling outdoor tempera
-
ture setting
°C
25
-127÷127
I
b12
Heating outdoor tempera
-
ture setting
°C
15
-127÷127
I
b13
Cooling temperature delta °C
-10.0
-50.0÷80.0
I
b14
Heating temperature delta °C
10.0
-50.0÷80.0
I
b15
0-10V analogue input set
-
ting decalibration band
°C
5.0
0.0÷10.0
I
b20
0-10V ratiometric input en
-
abling
/
0
0÷1
I
0 = 0-10V input
1 = Ratiometric input
b22
Plant probe temperature
control cut-off hysteresis
°C
5.0
0.0÷25.5
I
P01
Pump ON compressor ON
delay
sec
30
0÷255
I
P02
Pump OFF compressor OFF
delat
min
2.0
0÷25.5
I
P03
Pump operation mode
/
0
0÷1
I
The pump is always
on if the antifreeze
heaters are active.
P04
Pump setting in antifreeze
°C
5
-15÷15
I
P05
Pump hysteresis in anti
-
freeze
°C
2.0
0.0÷15.0
I
P09
Modulating pump inlet/out
-
let water delta T setting
°C
2.0
0÷15
I
P16
Interval between 2 periodi
-
cal activations of the pump
min
0
0÷600
I
P17
Operating time of the pump
in periodical mode
sec
0
0÷255
I
*r02
Antifreeze heaters setpoint
in heating mode
°C
4
3÷6
I
Only change if gly
-
col water is present.
Contat company.
*
r03
Antifreeze heaters setpoint
in cooling mode
°C
4
3÷6
I
Only change if gly
-
col water is present.
Contact company.
*
r06
Antifreeze heaters delta
°C
2.0
0.0÷25.5
I
Only change if gly
-
col water is present.
Contact company.
*r08
Operation in substitution
upper limit
°C
-20
-20÷50
I
Respect r22 ≥ r28 ≥ r08
Si consiglia di non
modificare tale va
-
lore, si potrebbe
c o m p r o m e t t e r e
il
funzionamento
dell’unità
*r10
System integration enabling /
0
0÷1
I
0 = Function disabled
1 = Function enabled
*r11
System integration heater
delta
°C
0.5
0,0÷25.5
I
*r12
Heater activation delay
DHW/heat pump integra
-
tion
min
10
0÷255
I
*r14
Exclusive resistor operation /
0
0÷1
I
0 = Resistors that can be activated
simultaneously
1 = Resistors that can be activated
exclusively
*r15
Enabling sanitary integra
-
tion
/
0
0÷2
I
0 = Function disabled
1 = Function enabled
*r16
Heater activation delay
DHW/heat pump integra
-
tion
min
15
0÷255
I
*r19
Duration of activation of
basin resistances from last
defrost
min
10
0÷255
I
0= activation of defrosting-indepen
-
dent resistor.
*r20
Priority use of resistors
/
1
0÷1
I
0 = Plant side priority
1 = Sanitary side priority
This parameter only
needs to be set if
r14=1
*r21
Enable systrem side mitiga
-
tion with defrosting resisi
-
tors
/
0
0÷1
I
0=Function disabed
1=Function enabled
*r22
Upper limit Joint function I
band
°C
7
-16÷50
I
Respect r22 ≥ r28 ≥ r08
It is recommended
not to change this
value, as this could
compromise the op
-
eration of the unit.
Summary of Contents for i-HPV5H 0140
Page 32: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 32...
Page 33: ...33 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...
Page 34: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 34...
Page 35: ...35 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...