Chillers and Inverter Air/Water heat pumps with axial fan

30

Register

Format

Bit

R/W

Range

Name

Description

Note

1001

°C/10

-

R/W

5.0 ÷ 23.0

Set point

Cooling

1002

°C/10

-

R/W 25.0 ÷ 55.0

Heating

1003

°C/10

-

R/W 25.0 ÷ 55.0

*Sanitary

If active

1004

°C/10

-

R/W

5.0 ÷ 23.0

Second cooling

If active

1005

°C/10

-

R/W 25.0 ÷ 55.0

Second heating

If active

240

BIT MASK

0 ÷ 1

R

General status

0= off

1 = on

2 = only sanitary

3 = remote on/off

2

System mode

0 = cool

1 = heat

3

Machine mode

0 = cool

1 = heat

4

Sanitary

0 = off

If active

1 = running

5 ÷ 7

Defrost status

0 = inactive
1 = starting

2 = active

3 = dripping

4 = finished

253

°C/10

-

R

-

Transducer tempera

-

tures

Evaporation

254

°C/10

-

R

-

Condensation

305

ora

-

R

-

Operating hours

Compressor 1

406

bar/100

-

R

-

Pressions

High

414

bar/100

-

R

-

Low

400

°C/10

-

R

-

Temperature

Water inlet

401

°C/10

-

R

-

Water outlet

405

°C/10

-

R

-

ACS

If active

428

°C/10

-

R

-

External

433

°C/10

-

R

-

Compressor 1 discharge

440

°C/10

-

R

-

Remote system

If active

7000

%/10

-

R

-

Analogue output

Condensaton fan

7001

%/10

-

R

-

Circulator pump

950

BOOL

0

R

-

ALARM - E01

* High pressure

Reset alarms use com

-

mand 6 to write the value 

0 to any of the registers 

in the alarm area.

1

ALARM - E02

* Low pressure

2

ALARM - E03

* Thermal compressor 1

3

ALARM - E04

* Thermal fan1

4

ALARM - E05

Ice

5

ALARM - E06

Flowswitch

6

ALARM - E07

*Low temperature DHW preparer

7

ALARM - E08

Forced compressor shutdown for 

lack of lubrication

8

ALARM - E09

High exhaust temperature

9

ALARM - E10

*High temperature solar collector

12

ALARM - E13

* Compressor 2 thermal

13

ALARM - E14

* Thermal fan2

15

ALARM - E16

*Thermal pump 1

951

BOOL

1

R

-

ALARM - E18

High temperature

9

ALARM - E26

*Thermal pump 2

11

ALARM - E41

Incongruent temperature

12

ALARM - E42

Insufficient heat exchanger

13

ALARM - E50

High temperature domestic hot 

water storage tank

14

ALARM - E101

Gi module disconnected

Summary of Contents for i-HPV5H 0140

Page 1: ...er any form of the texts and of the figures contained in this manual This manual is a translation from the official italian language version For reasons of environmental respect the Company will not p...

Page 2: ...B First emission Rev Date Compiled Approved Note Code Serie MCO01080100001 Chillers and inverter Air Water heat pumps with axial fans Controllo per i HPV5 Chillers and Inverter Air Water heat pumps w...

Page 3: ...NU PAR 10 4 9 OPERATING HOURS MENU OHR 10 4 10 LOG MENU HIST 10 4 11 FIRWARE VERSION MENU FIR 10 4 12 USB MENU USB 10 4 12 1 FIRMWARE UPDATE UPdF 10 4 12 2 PARAMETERS UPDATE UPPA 10 5 SYSTEM RESOURCES...

Page 4: ...YSTEM HEALTH INTEGRATION RESISTENCE 19 21 4 INTEGRATION RESISTANCE SELECTION MODE 19 21 5 CIRCULATOR MANAGEMENT WITH ACTIVE RESISTANCE 19 21 6 BOILER ENABLING 19 21 7 LOGIC OF INTEGRATION HEATERS AND...

Page 5: ...5 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 24 13 LACK OF VOLTAGE 28 24 14 UTILITIES BLOCK ALARM TABLE 28 25 MODBUS VARIABLES 29...

Page 6: ...on due to dangerous electrical voltage Indicates important information that the operator has to follow in order to guarantee the correct operation of the unit in complete safety Also indicates some ge...

Page 7: ...tivated and or modified at the same time Different values from the default values can compromise the correct operation of the unit in case of doubt on the value to set contact the company Only authori...

Page 8: ...e to a higher menu or to increase the parameter value DOWN key allows to move to a lower menu or to decrease the parameter value 4 1 2 LED Cooling mode LED is on if COOL or COOL SAN mode is selected H...

Page 9: ...0 C San2 Second sanitary setpoin 48 0 25 60 C Coo2 Second Summer setpoint 18 0 Coo 25 C Hea2 Second Winter setpoint 35 0 25 Hea C If sanitary function is enabled see par 12 4 4 PASSWORD MENU PSS Enter...

Page 10: ...can read firmware version uEr revision rEu and sub revision SUb 4 12 USB MENU USB This menu appears after entering the installer password only if a USB key containing the relevant update files is con...

Page 11: ...ion by default par 13 1 DO7 H85 XP 10 1 N XP 10 2 fase 6 HDW valve control Voltage output 230Vac 50Hz 2A AC1 see paragraph 12 Modbus RTU RS485 XC 1 1 GND XC 2 1 R XC 2 2 R Factory enabled with CM acce...

Page 12: ...nt set point will be set Coo Hea b15 2 With input at 50 the set point will be that set Coo Hea With input at 100 the current set point will be adjusted set Coo Hea b15 2 NOTE In cooling mode consideri...

Page 13: ...val of time P16 the circulator is turned on for a time equal to P17 seconds The function is disabled with P17 0 default The periodic function is suspended in the case of antifreeze mode intervention 8...

Page 14: ...during this function the flow switch alarm is disabled the maintenance technician must guarantee that there is water inside the system 9 COMPRESSOR ON OFF LOGIC The restart of compressors is in operat...

Page 15: ...see Chapter 5 and the relative control must also be enabled with parameter H85 6 default The domestic hot water DHW function is controlled through parameter H10 Parameter VALUE Function H19 6 DHW temp...

Page 16: ...ctrical bridge must be removed from the terminal block With the contact open the unit will be in stand by mode in this state the message E00 will appear on the display on the machine When the contact...

Page 17: ...2 0 Function not active 1 Enable Hz minimum L03 0 Function not active 1 Function active only in cooling mode 2 Function active only in heating mode 3 Function active only in sanitary mode 4 Function a...

Page 18: ...ed mode With the function active the noise output and power of the unit are limited for additional information see the installer user manual 20 PARTIAL RECOVERY WITH DESUPERHEATER IF DS ACCESSORY IS P...

Page 19: ...o lockout due to the intervention of an alarm It switches off when the machine finishes DHW production also taking into account any offset on the set point set with parameter r31 Parameter VALUE Funct...

Page 20: ...f boiler use r32 1 3 Boiler equipment 21 7 LOGIC OF INTEGRATION HEATERS AND OR BOILER IN JOINT OPERATION OR IN SUB STITUTION OF THE HEAT PUMP COMPRESSOR The auxiliary parts that can be used for joint...

Page 21: ...o thermoregulated by the system water remote probe as described above If the remote system water probe is not active the boiler is controlled by the flow probe of the heat pump 21 8 3 OPERATION IN SUB...

Page 22: ...r12 minutes plant inte gration heater HEAT HEAT SAN HEAT 1 0 1 2 Set the minutes 4 6 1 3 1 Heat pump 2 After r16 minutes DHW integration heater HEAT SAN SANITARY 0 1 1 Set the minutes 0 1 4 2 3 1 Hea...

Page 23: ...s 6 3 1 Plant DHW integration heater 2 After r12 minutes heat pump HEAT HEAT SAN HEAT SANITARY 1 1 Set the minutes Set the minutes 0 3 TABLE 4 OPERATION IN SUBSTITUTION INTERVENTION ORDER STATUS OPERA...

Page 24: ...unt are interrupted With remote on off contact open the Plant inte gration heater is deactivated Works as indicated in TABLES 1 2 3 and 4 COOL SAN DHW Cannot be actived Works as indicated in TABLE 5 C...

Page 25: ...I 0 Digital inputs N A 1 Polarit invertita di ID9 H77 Digital inputs polarity 0 0 255 I 0 Digital inputs N A 1 ID7E1 polarity inverted 2 ID8E1 polarity inverted 4 ID9E1 polarity inverted 8 ID10E1 pola...

Page 26: ...ter is present Contat company r03 Antifreeze heaters setpoint in cooling mode C 4 3 6 I Only change if gly col water is present Contact company r06 Antifreeze heaters delta C 2 0 0 0 25 5 I Only chang...

Page 27: ...a period of 10 seconds from the start of the machine after the bypass time the status of the digital input is considered if it is active the presence of flow is considered If a lack of flow is diagno...

Page 28: ...ber of alarm interventions in one hour is 3 the alarm becomes manual reset 24 12 E041 4 WAY VALVE This alarm identifies a malfunction of the 4 way valve for reversing and is manual reset The alarm is...

Page 29: ...g to your requirements you must modify the following parameters Parameter VALUE Function H124 0 Baud rate 4800 bit s 1 Baud rate 9600 bit s 2 Baud rate 19200 bit s 3 Baud rate 38400 bit s H125 0 Parit...

Page 30: ...nlet 401 C 10 R Water outlet 405 C 10 R ACS If active 428 C 10 R External 433 C 10 R Compressor 1 discharge 440 C 10 R Remote system If active 7000 10 R Analogue output Condensaton fan 7001 10 R Circu...

Page 31: ...module Gi Probe 11 If active 954 BOOL 1 R ALARM E801 Inverter link 1 2 ALARM E802 Inverter link 2 4 ALARM E851 Hardware fault inverter 1 5 ALARM E852 Hardware fault inverter 2 7 ALARM E861 Overcurrent...

Page 32: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 32...

Page 33: ...33 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...

Page 34: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 34...

Page 35: ...35 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...

Page 36: ...ADVANTIX SpA Via S Giuseppe Lavoratore 24 37040 Arcole VR Italy Tel 39 045 76 36 585 E mail info advantixspa it www maxa it...

Reviews: