11.2 ON-OFF LOGIC
Relay type
PV
Relay
LED
Hi-On
PV > SP
On
On
PV < SP
Off
Off
Open sensor
Up scale
On
On
Down scale
Off
Off
Low-On
PV > SP
Off
Off
PV < SP
On
On
Open sensor
Up scale
Off
Off
Down scale
On
On
11.3 Retransmission Output Table for OPEN /OVER /UNDER Condition
RETRASMISSION
VARIABLE
SCALE
ACTION
OPEN
OVER
UNDER
4-20mA
PV
UP
DIR
20.8
20.8
3.2
PV
DOWN
REV
3.2
3.2
20.8
PV
UP
REV
20.8
3.2
20.8
PV
DOWN
DIR
3.2
20.8
3.2
1-5V
PV
UP
DIR
5.2V
5.2V
0.8V
PV
DOWN
REV
0.8V
0.8V
5.2V
PV
UP
REV
5.2V
0.8V
5.2V
PV
DOWN
DIR
0.8V
5.2V
0.8V
NOTE: -
1.
OPEN/UNDER/OVER condition is applicable to all input types except 0-5v /
0-20mA.
11.4 Linear Output Table for OPEN/OVER/ UNDER Condition
CONTROL OP
Process
Scale
Output
Direction
(O.DIR)
DISPLAY INDICATION
OPEN
OVER
UNDER
4-20mamp
UP
DIR
20.0
20.0
4.0
Current
DOWN
REV
4.0
4.0
20.0
UP
REV
20.0
4.0
20.0
DOWN
DIR
4.0
20.0
4.0
SSR
UP
DIR
ON
ON
OFF
Pulse Output
DOWN
REV
OFF
OFF
ON
UP
REV
ON
OFF
ON
DOWN
DIR
OFF
ON
OFF
RELAY
UP
DIR
ON
ON
OFF
DOWN
REV
OFF
OFF
ON
UP
REV
ON
OFF
ON
DOWN
DIR
OFF
ON
OFF