Model: TC5396
masibus
Doc. Ref. no. : - m105/om/101
Issue no. 00
User’s Manual
Page 28 of 40
P ACTION: -
I Action: -
D Action: -
Control output Selection:
“COP
”
“OT”
Terminal
10,11,12
Terminal
7,8,9
Terminal
5,6
Terminal
3,4
Terminal
21, 22
Terminal
23, 24
PID
Relay
USE FOR
CONTROL
ACTION
ALARM2
ALARM3
ALARM4
AO output
AO
Output/
Communic
ation
SSR
USE FOR
CONTROL
ACTION
ALARM2
ALARM3
ALARM4
AO output
AO
Output/
Communic
ation
Linear
ALARM1
ALARM2
ALARM3
ALARM4
USE FOR
CONTROL
ACTION
AO
Output/
Communic
ation
VPFN
Forward
Relay
Revers
Relay
ALARM3
ALARM4
AO output
AO
Output/
Communic
ation
ON-
OFF
Actio
n
Relay
USE FOR
CONTROL
ON-OFF
ACTION
ALARM2
ALARM3
ALARM4
AO output
AO
Output/
Communic
ation
NOTE:-At a time either Relay or SSR is provided (factory set)
For Terminal 23,24 only one type of output is available.
(AO Output or Communication)(Factory Settable)
7.3 Ramp and Soak Function
This function is used to stop the sudden change of set point. The ramp function is
performed in following conditions. The target set point is changed. Target set point
number is changed. (For example: Switching from SP-1 to SP-2). The power is turned
ON or the controller is recovered from power failure. A change is made from manual
mode to auto mode.
When the
is in RUN mode and the process value crosses the set point value for the
first instant, a “soak period” begins.
Indication of “SOAK” in RUN mode: Decimal point of last digit of PV display is “ON”
The ramp function will be performed when ramp unit parameter is selected as
MInR
(minute rate) or
HRR
(hour rate). The ramp rate can be programmed by setting the
parameter
rmpr
.
The Soak rate is programmed by setting
sokr.
Soak time will be performed according to
shod
and
srst.
When the soak type is
shod
it will not reset the soak rate when the