Model: TC5396
masibus
Doc. Ref. no. : - m105/om/101
Issue no. 00
User’s Manual
Page 19 of 40
*
The value of FLTR will determine the ability of filtering noise. When a large value is set, the measurement input is stabilized
but the response speed is slow. Generally, if great interference exists, then you can increase parameter “FLTR” gradually
.
When the meter of the instrument is b
eing examined at laboratory, “FLTR” should be set to
0 or 1 to short the response time.
DP
(
dp
)
Decimal
Point
Set position of Decimal Point on Display.
0
/
1
/
2
/
3
*0 : 0
*1 : 0.0
2 : 0.00
3 : 0.000
1
Input Type is
Linear,
*if input type
is RTD or
TC(E,J,K,T)
26
DISP
(
disp
)
Display Set
Point
Set which Set Point to shown in SV display in
RUN mode while device is in Auto Mode
C1sp
/
A1sp
/
A2sp
/
A3sp
/
A4Sp
/
sOKR
0 : C1SP (Control Set Point 1)
1 : A1SP (Alarm Set Point 1)
2 : A2SP (Alarm Set Point 2)
3 : A3SP (Alarm Set Point 3)
4 : A4SP (Alarm Set Point 4)
5: SOKR (Remaining Soak Time)
0
Output Type
is Linear ,
only then
A1.SP will
appear.
27
OFST
(
ofst
)
offset
Offset Value
Input type
range
RTD/ Thermocouple
-100.0°C to +100.0°C
Linear
-1000 to +1000
0.0
28
FLTR*
(
fltr
)
Filter
Enable or Disable Filter for PV Input
0
/
1
/
2
/
3
/
4
/
5
4
29
A.CJC
(
a.CJC
)
Auto
Cold
Junction
Compensatio
n
Select Auto Cold Junction Compensation
required or not for TC input Type.
no
/
yes
0 : NO
1 : YES
1
(YES)
Input Type is
TC
30
F.CJC
(
F.CJC
)
Fix
cold
junction
Compensatio
n
Set Fix cold junction Compensation value.
0 to 60.0 °C
0.0
Input Type is
TC & A.CJC is
NO
31
RD1
(
rd1
)
Relay Delay
(For Relay-1)
Relay Delay is amount of time (in sec), that
Relay will wait before getting ON after the ON
condition occurs.
1 to 99 sec
1 sec
Control Type
(COP) is ON-
OFF.
32
HY-1
(
Hy-1
)
Hysteresis
–
1
(For Relay-1)
Hysteresis Value (in °C) for Relay-1 during ON-
OFF type Control.
1 to 250
TC & RTD Input
1 to 250
Linear Input with DP=0
0.1 to 25.0
Linear Input with DP=1
0.01 to 2.50
Linear Input with DP=2
0.001 to 0.250
Linear Input with DP=3
1
Control Type
(COP) is ON-
OFF.
33