Model: TC5396
masibus
Doc. Ref. no. : - m105/om/101
Issue no. 00
User’s Manual
Page 16 of 40
6.2 RUN Time Indication/Function
Following parameters can view or change during run time.
Press Decrement key to show percentage power Auto Mode (0.0 to 100.0%)
For Thermocouple input type, Press Increment key to show ambient
temperature.
During manual mode, Increment key and Decrement Key will use to
modify the percentage power.
TC5396 can be configured as PID or ON-OFF Controller.
On selection of PID / ON-OFF, only relevant parameters will be displayed in
menu.
Press
for at least 2 sec to toggle between AUTO & MANUAL
mode if function key is A/M.
6.3 LEVEL 1 SET POINT SETTINGS
Set Point Setting:
Parameter
(PV display) Setting name and
description
Default
value
Shows only if
Reg.
No.
Symbol Name
C1SP
(
C1sp
)
Control
Set
Point 1
Range Depending on PV
sensor type selected
100
-
1
A1SP
(
A1sp
)
Alarm
Set
Point 1
Range Depending on PV
sensor type selected
100
Output Type is
LIN(Linear)
2
A2SP
(
A2sp
)
Alarm
Set
Point 2
Range Depending on PV
sensor type selected
100
-
3
A3SP
(
A3SP
)
Alarm
Set
Point 3
Range Depending on PV
sensor type selected
100
4
A4SP
(
A4SP
)
Alarm
Set
Point 4
Range Depending on PV
sensor type selected
100
5