6.5 LEVEL 3 CONFIGURATION MODE
SOKT
(
SOKT
)
Soak type
shod
/
srst
0:shod
1:srst
srst
18
CONFIGURATION PARAMETERS
Parameter
(PV display)
Setting Name & Description
Default
Value
Show if
Only
Reg.
No.
Symbol
Name
INPT
(
inpt
)
INPUT Type
Set PV Input Type
tC e
/
tC j
/
tC K
/
tC t
/
tC b
/
tC r
/
tC s
/
rtd
/
0-10
Value
Input Type
Range
0
TC E
-200 to 1000 °C
1
TC J
-200 to 1200 °C
2
TC K
-200 to 1372 °C
3
TC T
-200 to 400 °C
4
TC B
450 to 1800 °C
5
TC R
0 to 1768 °C
6
TC S
0 to 1768 °C
7
RTD
-199.9 to 850.0 °C
8
0-10 V
-1999 to 9999
*
Use external 250ohms,0.1% for current
input
TC E
19
ZERO
(
zero
)
Zero
Automatically change to the Input Lower Range
with changing of Input Type
(Refer Above Table)
Can be set to any value within the Input Range
& less the SPAN Value.
-200
(If TC E)
20
SPAN
(
span
)
Span
Automatically change to the Input Higher Range
with changing of Input Type
(Refer Above Table)
Can be set to any value within the Input Range
& greater the ZERO Value.
1000
(If TC E)
21
INLO
(
INLO
)
Input low
Range
Input low range between 0.0 to 10.0
(It will be always less then INHI)
0.0
Input type is
0-10V
22
INHI
(
INHI
)
Input High
Range
Input High range between 0.0 to 10.0
(It will be always greater then INLO)
10.0
Input type is
0-10V
23
TSP1
(
tsp1
)
Type of Set
Point
Set Type of Set Point
l-on
/
H-on
0 : L-ON (Lower ON)
1 : H-ON (Higher ON)
0
(L -O N)
Control Type
(COP) is ON-
OFF.
24
OPES
(
opes
)
OPEN Sensor
Status
Set Control O/P & Retransmission state when
Input OPEN condition.
down
/
up
0 : DOWN
1 : UP
Refer
Retransmission Output Table for OPEN
Table for OPEN/OVER/ UNDER Condition
1
(UP )
2 5