User Manual
P a g e
|
29
of
49
Decimal Point for this EditBox can be changeable.
This parameter is enabled, if
Main Display
in
MENU
DISPLAY
SOURCE
is set to
Scaled.
TF
(Transfer Function)
Transfer Function for Scaling
Available Options:
Linear
x^2 (x
2
)
x^(1/2) (
√x)
This parameter is enabled, if
Main Display
in
MENU
DISPLAY
SOURCE
is set to
Scaled.
Source Type
Source Output Format
Available Options:
STEP
RAMP
At a time one can be selectable.
Press F1 key on the one of the option for more settings.
4.2.1 STEP Page
Parameter Name
Description / Options
Manual
(Output Type)
Step Manual Mode Selection CheckBox.
Ticking this checkbox will enable Step Manual Mode. And Un-ticking will
enable Auto Step Mode.
Step Time (s)
Enter the time for a single step in seconds,
Range:
1 to 9999
This parameter is enabled only for Auto Step Mode (Manual CheckBox is
Un-Checked)
Step(unit)
Step Size in unit
Step Size in unit, where unit is changed according to current Output Type
and Source Display Mode.
Only Specify one Step(unit) or Step(%), the other will automatically
changed according to the changed parameter.