28
of
49|
P a g e
UserManual
4.2 SOURCE Page
This Page is appears in
RUN
MENU
SOURCE.
This page contains parameters related to Measure like Output Type,
Output Range, Scaling, Transfer Function Step and Ramp. The
Description of the Parameters appear on this page is given below.
Parameter Name
Description / Options
O/P Type
(Output Type)
Source Output Type
Available Options:
mA : 0.000 to 24.000 mA DC
mA(2W) : 0.000 to 24.000 mA DC
mV : 0.00 to 250.00 mV DC
V : 0.000 to 12.000 V DC
Output Range
Low (0%)
Low Range for Source Output.
Range:
Default Output Low to
Output Range High(100%)
This parameter is enabled, if
Main Display
in
MENU
DISPLAY
SOURCE
is set to
Percentage
or
Scaled.
Output Range
High (100%)
High Range for Source Output.
Range:
Output Range Low(0%)
to Default Output High
This parameter is enabled, if
Main Display
in
MENU
DISPLAY
SOURCE
is set to
Percentage
or
Scaled.
Scaled Output Range
Low(0%)
Scaling Low Range for Source Output.
Range:
-99999 to
Scaled Output Range High(100%)
Decimal Point for this EditBox can be changeable.
This parameter is enabled, if
Main Display
in
MENU
DISPLAY
SOURCE
is set to
Scaled.
Scaled Output Range
High(100%)
Scaling High Range for Source Output
Range:
Scaled OutputRange Low(0%)
to 99999