3.  All  3  phase  motors  are  bi-directional,  which  means 

they  can  rotate  in  either  direction.  Follow  directional 
arrows  on  the  blower  wheel  housings  for  proper 
rotation.  If  the  motor  is  rotating  incorrectly,  switch  two 
of the 3 phase power or motor leads and the motor will 
rotate the opposite direction. Make sure all motors are  
turning in the same and proper direction. (FIG. 3) 

 

    FIG. 3 
 
 
 

NOTE 

 

For accessory installation, reference Accessory 
Installation Supplement. 

 

For heated products, reference Heated Products 
Supplement.

 

 
 

START-UP 
 

This  product  has  been  assembled  and  tested  at  the 
factory  prior  to  shipping.  The  following  procedures 
should  be  performed  to  assure  its  performance.  Before 
continuing with the start-up, it is  important  to recognize

 

the safety controls furnished with the unit. 

 
 

 
 

 
 

 

        WARNING 

Prevent hazard of electrical shock.  More than one 
disconnect switch may be required to de-energize this 
product. 

 

        WARNING 

 
The following items must all be completed by a qualified 
installer and checked off when completed 
 
A.  Re-check that the product has been installed 

properly and is level and secure. 

B.  Check all terminal screws are tight and field wiring is 

connected in accordance to National Electrical Code 
and wired per the enclosed wiring diagram. For 
electric heated models, ensure that the coils are 
secured and not touching each other on any metal 
surface. 

C.  Verify proper voltage prior to powering the product. 

(See product label for reference). 

D. 

Check all field wired components “if supplied” are 
wired correctly. 

E.  Check that the inlet air supply and the discharge air 

supply are free of obstructions. 

F.  Check that all air filter(s) and/or air intake grille(s) are 

in place and installed properly, as originally shipped. 

G.  Verify voltage to the product once more and turn 

power on. 

H.  Regardless of whether the product is mounted on the 

inside or outside of the door opening, set the air 
directional vanes in the discharge nozzle slightly 
outward to approximately 10-15° towards the outside, 
or the wind load. (FIG. 4). 
 

 
 
 
 
I. 

For products with control panels, turn the HOA 
(Hand-On-

Auto) selector switch to “On” position and 

open the door to energize the product. For products 
without a control panel or an On/Off switch, open the 
door to energize the product. 

J.  If heated products are installed, reference 

Heated 

Products Supplement

.  

K.  For three phase units, verify direction of rotation of 

blower wheels (note direction arrows on the blower 
wheel housing). Correct if needed by changing 
polarity of three phase power. 

FIG. 4 

Summary of Contents for PH10 Unheated Series

Page 1: ...ithout notice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA PH10 Unheat...

Page 2: ...notice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Table of Contents...

Page 3: ......

Page 4: ...lumns to complete the model numbers AMCA Certified Lab Data Model Distance from nozzel in Avg Core Velocity FPM 40 1089 80 1000 120 900 160 822 Projection Velocity PH1036 1U Unheated Data Sheet Applic...

Page 5: ......

Page 6: ...oor type door limit switch installation FIG 1 2 Use light gauge materials when field fabricating brackets to activate and deactivate the door limit switch s FIG 2 Figure 2 also shows the typical insta...

Page 7: ...nded Wall Mounting For Tandem Mounting of air curtain over sectional style door use either wall mounting angle brackets or threaded rods 4 Top Mounting Brackets For overhead installation of units use...

Page 8: ...ies are 1 2 HP and 1 HP respectively The Phantom Series come standard with an air intake screen s GENERAL SAFETY INFORMATION Use this product only in the manner intended by the manufacturer If you hav...

Page 9: ...e screen can be removed from the unit by pulling the spring loaded piano hinges FIG 1 3 All Phantom series have the Motor Fan Assembly MFA shipped internally mounted 4 All units are equipped with 4 3...

Page 10: ...connected in accordance to National Electrical Code and wired per the enclosed wiring diagram For electric heated models ensure that the coils are secured and not touching each other on any metal surf...

Page 11: ...he outdoor elements Contact factory for special construction and costing Freezer and Cooler Installation Air curtain must be mounted on the warm side for optimal performance Variable Frequency Drive V...

Page 12: ...in this manual Obstruction on intake or discharge Remove obstruction or move air curtain Power leads out of polarity Switch power leads to correct polarity 3 phase models only Blower motor rotating be...

Page 13: ...esponsible for transportation charges associated with replacement of failed part Mars does not warrant uninterrupted or error free operation of Mars product Under no circumstance is Mars liable for an...

Page 14: ...g Metal Studs D Section 07900 Joint Sealers E Section 08110 Steel Doors and Frames F Section 08330 Overhead Coiling Doors G Section 15145 Plumbing Piping Gas piping to units H Section 15182 Hydronic P...

Page 15: ...1 Standard for Fixed and Location Dedicated Electric Room Heaters Intertek Testing Services Listed for US and Canada I CSA 3812 01 Fans and Blowers Certified to US Standards Canadian Standard Associat...

Page 16: ...tions trouble shooting guide parts list and electrical wiring diagrams 1 5 QUALITY ASSURANCE A Manufacturer Qualifications Minimum ten years documented experience producing the products specified in t...

Page 17: ...2 AIR CURTAIN ASSEMBLIES A Motor Fan Assembly Design for easy removal assembly repair and maintenance 1 Motor Totally enclosed air over TEAO cooled motor with sealed lifetime pre lubricated ball bear...

Page 18: ...ghts to 10 feet 3048 mm 1 Discharge Nozzle Wedge shaped discharge outlet nozzle with adjustable air foil vanes with a plus minus 40 degree sweep front to back 2 Air Velocity at Nozzle a PH10 36 1 36 I...

Page 19: ...ized steel bolted to air curtain housing 8 Supply and return fittings on ends of casing 9 Thermostat Wall mounted 110 Volt operation with heater on off selection C Hot Water Heaters Provide finned tub...

Page 20: ...trol panel Provide a separate control panel for three phase motors controlled by a limit switch 1 Type Combination plunger roller switch for swing and sliding doors a Provide limit switches with NEMA...

Page 21: ...st air curtains to function properly B Adjust air foil vanes located within the discharge nozzle as required for prevailing conditions at each opening C Check heated air curtain performance on a calm...

Page 22: ...ing changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Reference Links Link Description http marsair com Main website http marsair co...

Reviews: