background image

 

 

 

                                                                                              

 

15831-6 

 

b. 

Type: Fixed air intake grille. 
1) 

Filter: Aluminum mesh, 1/4 inch (6.4 mm), washable. 

c. 

Type: Filter Only as follows: 
1) 

Filter: Flat bank 1 inch, disposable. 

2) 

Filter: Aluminum mesh, 1/4 inch (6.4 mm), washable. 

d. 

Speed: 2550 cu ft/min (1200 L/s), minimum, per motor/fan assembly. 

5. 

Sound Pressure Level At 10 feet (3 m) From Nozzle: 
a. 

Single Motor/Fan Units:  66 dBA. 

b. 

Two Motor/Fan Units:  68 dBA. 

c. 

Three Motor/Fan Units:  71 dBA. 

d. 

Four Motor/Fan Units:  73 dBA. 

 
2.3 COMPONENTS 
 

A. 

Electric Heaters:  Provide complete with motor control panel factory mounted to air 
curtain housing, and thermostat to be field installed. 
1. Temperature 

limit 

controller. 

2. 

Thermostat:  Wall-mounted, 24-Volt operation, with heater on/off selection. 

3. 

Heating Coils: UL approved. Factory mounted on the discharge end of the 
motor fan assembly and located within the nozzle outlet. 

 

B. 

Steam Heaters:  Provide finned tube steam coils for field mounting on air intake side 
of the air curtain cabinet with opposite end connections. 
1. 

Output:  Air curtain manufacturer's standard, one-row coils. 

2. 

Output:  Air curtain manufacturer's standard, two-row coils. 

3. 

Coils: Certified in accordance with ARI 410. 

4. 

Connections: Opposite end. 

5. 

Connections: Same end, right hand. 

6. 

Connections: Same end, left hand. 

7. 

Casing:  One piece unpainted galvanized steel, bolted to air curtain housing. 

8. 

Supply and return fittings on ends of casing. 

9. 

Thermostat:  Wall-mounted, 110-Volt operation, with heater on/off selection. 

 

C. 

Hot Water Heaters:  Provide finned tube water coils for field mounting on air intake 
side of the air curtain cabinet with opposite end connections. 
1. 

Output:  Air curtain manufacturer's standard, one-row coils. 

2. 

Output:  Air curtain manufacturer's standard, two-row coils. 

3. 

Coils: Certified in accordance with ARI 410. 

4. 

Connections: Opposite end. 

5. 

Connections: Same end, right hand. 

6. 

Connections: Same end, left hand. 

7. 

Casing:  One piece unpainted galvanized steel, bolted to air curtain housing. 

8. 

Supply and return fittings on top of casing. 

9. 

Thermostat:  Wall-mounted, 110-Volt operation, with heater on/off selection. 

 
 

D. 

Motor Control Panels For Unheated Units: Recommended for all three phase units 
and single phase units with combined motor capacities of more than 1HP whenever 
a door limit switch is used to automatically start and stop the air curtain. Provide 
motor control panels as follows: 
1. 

Mounting: Factory mounted on right hand side of air curtain housing. 

2. 

Mounting: Factory mounted on left hand side of air curtain housing. 

3. 

Electrical components UL/CUL listed. 

E. 

Motor Control Panels For Electric Heated Units: Recommended for all three phase 
units and single phase units with combined motor capacities of more than 1HP 
whenever a door limit switch is used to automatically start and stop the air curtain. 

Summary of Contents for PH10 Unheated Series

Page 1: ...ithout notice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA PH10 Unheat...

Page 2: ...notice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Table of Contents...

Page 3: ......

Page 4: ...lumns to complete the model numbers AMCA Certified Lab Data Model Distance from nozzel in Avg Core Velocity FPM 40 1089 80 1000 120 900 160 822 Projection Velocity PH1036 1U Unheated Data Sheet Applic...

Page 5: ......

Page 6: ...oor type door limit switch installation FIG 1 2 Use light gauge materials when field fabricating brackets to activate and deactivate the door limit switch s FIG 2 Figure 2 also shows the typical insta...

Page 7: ...nded Wall Mounting For Tandem Mounting of air curtain over sectional style door use either wall mounting angle brackets or threaded rods 4 Top Mounting Brackets For overhead installation of units use...

Page 8: ...ies are 1 2 HP and 1 HP respectively The Phantom Series come standard with an air intake screen s GENERAL SAFETY INFORMATION Use this product only in the manner intended by the manufacturer If you hav...

Page 9: ...e screen can be removed from the unit by pulling the spring loaded piano hinges FIG 1 3 All Phantom series have the Motor Fan Assembly MFA shipped internally mounted 4 All units are equipped with 4 3...

Page 10: ...connected in accordance to National Electrical Code and wired per the enclosed wiring diagram For electric heated models ensure that the coils are secured and not touching each other on any metal surf...

Page 11: ...he outdoor elements Contact factory for special construction and costing Freezer and Cooler Installation Air curtain must be mounted on the warm side for optimal performance Variable Frequency Drive V...

Page 12: ...in this manual Obstruction on intake or discharge Remove obstruction or move air curtain Power leads out of polarity Switch power leads to correct polarity 3 phase models only Blower motor rotating be...

Page 13: ...esponsible for transportation charges associated with replacement of failed part Mars does not warrant uninterrupted or error free operation of Mars product Under no circumstance is Mars liable for an...

Page 14: ...g Metal Studs D Section 07900 Joint Sealers E Section 08110 Steel Doors and Frames F Section 08330 Overhead Coiling Doors G Section 15145 Plumbing Piping Gas piping to units H Section 15182 Hydronic P...

Page 15: ...1 Standard for Fixed and Location Dedicated Electric Room Heaters Intertek Testing Services Listed for US and Canada I CSA 3812 01 Fans and Blowers Certified to US Standards Canadian Standard Associat...

Page 16: ...tions trouble shooting guide parts list and electrical wiring diagrams 1 5 QUALITY ASSURANCE A Manufacturer Qualifications Minimum ten years documented experience producing the products specified in t...

Page 17: ...2 AIR CURTAIN ASSEMBLIES A Motor Fan Assembly Design for easy removal assembly repair and maintenance 1 Motor Totally enclosed air over TEAO cooled motor with sealed lifetime pre lubricated ball bear...

Page 18: ...ghts to 10 feet 3048 mm 1 Discharge Nozzle Wedge shaped discharge outlet nozzle with adjustable air foil vanes with a plus minus 40 degree sweep front to back 2 Air Velocity at Nozzle a PH10 36 1 36 I...

Page 19: ...ized steel bolted to air curtain housing 8 Supply and return fittings on ends of casing 9 Thermostat Wall mounted 110 Volt operation with heater on off selection C Hot Water Heaters Provide finned tub...

Page 20: ...trol panel Provide a separate control panel for three phase motors controlled by a limit switch 1 Type Combination plunger roller switch for swing and sliding doors a Provide limit switches with NEMA...

Page 21: ...st air curtains to function properly B Adjust air foil vanes located within the discharge nozzle as required for prevailing conditions at each opening C Check heated air curtain performance on a calm...

Page 22: ...ing changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Reference Links Link Description http marsair com Main website http marsair co...

Reviews: