SWING OPERATOR
-
INSTALLATION MANUAL
ID
DESCRIPTION
SETTINGS
DEFAULT
05
Return closing speed with spring
(VECTORM)
RANGE: 1 ÷ 9
(1 = minimum speed, 9 = maximum speed)
5
Wind protection function with the
door closed (VECTORM)
RANGE: 0 ÷ 9
(0 = wind protection deactivated, 9 = maximum wind protection)
0
06
Crushing protection
RANGE: 1 ÷ 9 both opening and closing
(1 = most sensitive ; 9 = least sensitive)
5
07
Accelerations
RANGE: 5 ÷ 30
(Regulating steps of 1) Modifies both accelerations and
decelerations
30
08
Approach angle
RANGE: 10 ÷ 40
[modifies both values (close equal to half (1/2) of the opening)]
20
09
Electronic lock control voltage
0 = 12 VDC
1 = 24 VDC
0
10
Electronic lock types
0 = Not used
For electronic lock types that may be used, see section
‘Management of Electronic Locks’
0
11
Electronic lock impulse duration
or opening delay
RANGE: 0 ÷ 9
The time depends on the type of electronic lock:
see section ‘Management of Electronic Locks’
2
12
Electronic lock closing force
RANGE: 0 (min.) ÷ 9 (max.)
5
13
Individual/double mode
0 = Individual
1 = Double Master
2 = Double Slave
0
14
Activation of the electronic lock
according to the selected logic
settings
0 = Deactivated
1 = One Radar
2 = Two Radars
3 = One Radar and Two Radars
3
15
Configuration of the auxiliary
input AUX
-
IN 1
0 = Disabled persons opening
1 = Emergency opening
2 = Door interlocking with priority
3 = Door interlocking without priority
4 = Lock release feedback
5 = Lock release control
6 = Individual control with operational mode with Double
7 = Puts the door in stand
-
by (if it is active)
8 = Resets door stand
-
by
9 = Step
-
step (1 impulse opens, 1 impulse closes)
10 = Fire alarm
11 = Manual operation
12 = Door closed
0
16
Configuration of the auxiliary
Input AUX
-
IN 2
0 = Disabled persons opening
1 = Emergency opening
2 = Door interlocking with priority
3 = Door interlocking without priority
4 = Lock release feedback
5 = Lock release control
6 = Individual control with operational mode with Double
7 = Puts the door in stand
-
by (if it is active)
8 = Resets door stand
-
by
9 = Step
-
step (1 impulse opens, 1 impulse closes)
10 = Fire alarm
11 = Manual operation
12 = Door closed
1
17
Configuration of the
auxiliary output AUX
-
OUT 1
0 = Monitoring the sensors
1 = Interlocking
2 = Open
-
door state
3 = Closed
-
door state
4 = Malfunction
5 = Lock control repetition
0
18
Configuration of the
auxiliary output AUX
-
OUT 2
0 = Monitoring the sensors
1 = Interlocking
2 = Open
-
door state
3 = Closed
-
door state
4 = Malfunction
5 = Lock control repetition
1
Summary of Contents for VECTOR
Page 1: ...Installation Manual VECTOR Operator ...
Page 15: ...14 D00619EN v0 SWING OPERATOR INSTALLATION MANUAL 5 4 A 5 4 B Fig 4 Fig 5 D A B E C F ...
Page 16: ...15 D00619EN v0 SWING OPERATOR INSTALLATION MANUAL 5 4 C 5 4 D Fig 6 Fig 7 A A A A ...
Page 19: ...18 D00619EN v0 SWING OPERATOR INSTALLATION MANUAL 5 5 A 5 5 B Fig 12 Fig 13 A A ...
Page 47: ...46 D00619EN v0 SWING OPERATOR INSTALLATION MANUAL CARACTERÍSTICAS MECÁNICAS 10 4 Notes ...