Discharge Line Temperature Analysis
GENERAL
Knowing if the discharge line temperature is
increasing, decreasing or remaining constant can be
an important diagnostic tool. Compressor discharge
line temperature on a normally operating ice machine
steadily increases throughout the freeze cycle.
Ambient air temperatures affect the discharge line
temperature.
Higher ambient air temperatures at the condenser
and/or higher inlet water temperature = higher
discharge line temperatures at the compressor.
Lower ambient air temperatures at the condenser and/
or lower supply water temperature= lower discharge
line temperatures at the compressor.
Regardless of ambient and water temperatures, the
freeze cycle discharge line temperature will be higher
than 150°F (66°C) [S850/S1000 Air & Water Machines
Only - 140°F (60°C)] at the end of the freeze cycle.
PROCEDURE
Connect a temperature probe on the compressor
discharge line with-in 6" of the compressor and
insulate
.
Observe the discharge line temperature for the last
three minutes of the freeze cycle and record on the
table.
Discharge Line Temperature Above 150°F (66°C)
[S850/S1000 Air & Water Machines Only - 140°F
(60°C)]
At End Of Freeze Cycle:
Ice machines that are operating normally will have
consistent minimum discharge line temperature of
150°F (66°C) [S850/S1000 Air & Water Machines Only
- 140°F (60°C)].
Summary of Contents for S300
Page 2: ......
Page 20: ...20 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number 80 1479 3 7 10 A B C D E ...
Page 45: ...Part Number 80 1479 3 7 10 45 A B C D E F G ...
Page 48: ...48 Part Number 80 1479 3 7 10 A A B C D E F G H I ...
Page 79: ...Part Number 80 1479 3 7 10 79 This Page Intentionally Left Blank ...
Page 80: ...80 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 133: ...Part Number 80 1479 3 7 10 133 This Page Intentionally Left Blank ...
Page 134: ...134 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 175: ...Part Number 80 1479 3 7 10 175 REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 184: ...184 Part Number 80 1479 3 7 10 SV1406 USING PINCH OFF TOOL ...
Page 189: ...Part Number 80 1479 3 7 10 189 This Page Intentionally Left Blank ...
Page 190: ...190 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 296: ...296 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 297: ...Part Number 80 1479 3 7 10 297 This Page Intentionally Left Blank ...
Page 298: ...298 Part Number 80 1479 3 7 10 ...
Page 299: ......