5. Using the information gathered, refer to the chart
below.
NOTE:
A head pressure control valve that will not
bypass, will function properly with condenser air
temperatures of approximately 70°F (21°C) or above.
When the temperature drops below 70°F (21°C), the
head pressure control valve fails to bypass and the ice
machine malfunctions. Lower ambient conditions can
be simulated by rinsing the condenser with cool water
during the freeze cycle.
Condition
Probable
Cause
Corrective
Measure
Discharge Pressure - High
Liquid Line Temperature -
Hot
Valve stuck in
bypass
Replace
valve
Discharge Pressure - Low
Liquid Line Temperature -
Cold
Valve not
bypassing
Replace
valve
Discharge Pressure - Low
Liquid Line Temperature -
Hot
Ice Machine
Low on
Charge
Low on
Charge
Verification
Summary of Contents for S300
Page 2: ......
Page 20: ...20 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number 80 1479 3 7 10 A B C D E ...
Page 45: ...Part Number 80 1479 3 7 10 45 A B C D E F G ...
Page 48: ...48 Part Number 80 1479 3 7 10 A A B C D E F G H I ...
Page 79: ...Part Number 80 1479 3 7 10 79 This Page Intentionally Left Blank ...
Page 80: ...80 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 133: ...Part Number 80 1479 3 7 10 133 This Page Intentionally Left Blank ...
Page 134: ...134 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 175: ...Part Number 80 1479 3 7 10 175 REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 184: ...184 Part Number 80 1479 3 7 10 SV1406 USING PINCH OFF TOOL ...
Page 189: ...Part Number 80 1479 3 7 10 189 This Page Intentionally Left Blank ...
Page 190: ...190 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 296: ...296 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 297: ...Part Number 80 1479 3 7 10 297 This Page Intentionally Left Blank ...
Page 298: ...298 Part Number 80 1479 3 7 10 ...
Page 299: ......