HARVEST ASSIST AIR PUMP
FUNCTION
The air pump breaks the vacuum between the sheet of
ice and the evaporator which results in shorter harvest
cycles.
SPECIFICATIONS
115 Volt or 230 Volt - matches the ice machine
voltage.
CHECK PROCEDURE
1. Verify when the air pump should be running in the
sequence of operation.
2. If the compressor is not running when it should be
check voltage at the control board.
3. If there is no voltage present at the control board,
replace the control board.
4. If there is voltage present at the control board
check for voltage at the air pump connector.
5. If there is no voltage present at the air pump
connector replace wire.
6. If there is voltage at the air pump connector, use a
volt ohm meter to verify there is no continuity
through the motor windings then replace motor.
Summary of Contents for S300
Page 2: ......
Page 20: ...20 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number 80 1479 3 7 10 A B C D E ...
Page 45: ...Part Number 80 1479 3 7 10 45 A B C D E F G ...
Page 48: ...48 Part Number 80 1479 3 7 10 A A B C D E F G H I ...
Page 79: ...Part Number 80 1479 3 7 10 79 This Page Intentionally Left Blank ...
Page 80: ...80 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 133: ...Part Number 80 1479 3 7 10 133 This Page Intentionally Left Blank ...
Page 134: ...134 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 175: ...Part Number 80 1479 3 7 10 175 REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 184: ...184 Part Number 80 1479 3 7 10 SV1406 USING PINCH OFF TOOL ...
Page 189: ...Part Number 80 1479 3 7 10 189 This Page Intentionally Left Blank ...
Page 190: ...190 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 296: ...296 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Page 297: ...Part Number 80 1479 3 7 10 297 This Page Intentionally Left Blank ...
Page 298: ...298 Part Number 80 1479 3 7 10 ...
Page 299: ......