Electrical System
Section 6
6-52
Part No. 80-1100-3
Problem: Water Trough Overfilling During The
Freeze Cycle (continued)
Step 3
Allow ice machine to run. Disconnect the water
level probe from control board terminal 1F, and connect
a jumper wire from terminal 1F to any cabinet ground.
1
Remember if you are past 6 minutes from starting, the
ice machine will go into a freeze cycle water inlet valve
safety shut-off mode, and you will be unable to complete
this test. If past 6 minutes you must restart this test by
disconnecting the jumper wire, restarting the ice
machine, (step 1) and then reinstalling the jumper wire to
terminal 1F, after the compressor starts.
Figure 6-27. Step 3
Step 3 Jumper wire connected from control board terminal 1F to ground
Is water flowing into
the water trough?
The Water Level
Light is:
The Water Inlet Valve
Solenoid Coil is:
Cause
no
on
De-Energized
The water level probe is causing the problem.
Clean or replace the water level probe.
yes
off
Energized
The control board is causing the problem.
yes
on
De-Energized
The water fill valve is causing the problem.
SV1588b
CLEAN LIGHT
WATER LEVEL LIGHT
BIN SWITCH LIGHT
HARVEST/SAFETY LIMIT LIGHT
1C
1F
YELLOW
GREEN
GREEN
RED
JUMPER
G R O U ND
Summary of Contents for QD0202A
Page 3: ......
Page 14: ...General Information Section 1 1 4 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 34: ...Installation Instructions Section 2 2 20 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...Maintenance Section 3 3 16 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 93: ...Section 6 Electrical System Part No 80 1100 3 6 37 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...Electrical System Section 6 6 56 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 135: ...Section 7 Refrigeration System Part No 80 1100 3 7 23 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 168: ...Refrigeration System Section 7 7 56 Part No 80 1100 3 Figure 7 18 Using Pinch Off Tool SV1406 ...
Page 174: ...Refrigeration System Section 7 7 62 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 175: ...Section 7 Refrigeration System Part No 80 1100 3 7 63 THIS PAGE INTENTIONALLY LEFT BLANK ...