Section 2
Installation Instructions
Part No. 80-1100-3
2-15
CALCULATING REMOTE CONDENSER
INSTALLATION DISTANCES
Line Set Length
The maximum length is 100' (30.5 m).
The ice machine compressor must have the proper oil
return. The receiver is designed to hold a charge
sufficient to operate the ice machine in ambient
temperatures between -20°F (-28.9°C) and 120°F
(49°C), with line set lengths of up to 100' (30.5 m).
Line Set Rise/Drop
The maximum rise is 35' (10.7 m).
The maximum drop is 15' (4.5 m).
Calculated Line Set Distance
The maximum distance is 150' (45.7 m).
Line set rises, drops, horizontal runs (or combinations of
these) in excess of the stated maximums will exceed
compressor start-up and design limits. This will cause
poor oil return to the compressor.
Make the following calculations to make sure the line set
layout is within specifications.
1. Insert the
measured rise
into the formula below.
Multiply by 1.7 to get the
calculated rise.
(Example: A condenser located 10 feet above the
ice machine has a
calculated rise
of 17 feet.)
2. Insert the
measured drop
into the formula below.
Multiply by 6.6 to get the
calculated drop.
(Example. A condenser located 10 feet below the
ice machine has a
calculated drop
of 66 feet.)
3. Insert the
measured horizontal distance
into the
formula below. No calculation is necessary.
4. Add together the
calculated rise, calculated drop,
and
horizontal distance
to get the
total calculated
distance.
If this total exceeds 150' (45.7 m), move
the condenser to a new location and perform the
calculations again.
Maximum Line Set Distance Formula
!
Caution
If a line set has a rise followed by a drop, another
rise cannot be made. Likewise, if a line set has a
drop followed by a rise, another drop cannot be
made.
Step 1.
Measured Rise (35' [10.7 m] Maximum)
______ x 1.7
=
_______ Calculated Rise
Step 2.
Measured Drop (15' [4.5 m] Maximum)
______ x 6.6
=
_______ Calculated Drop
Step 3.
Measured Horizontal Distance (100' [30.5 m] Maximum)
_______ Horizontal Distance
Step 4.
Total Calculated Distance 150' (45.7 m)
_______ Total Calculated Distance
H
R
H
D
H
D
R
Figure 2-6. Combination of a Rise
and a Horizontal Run
Figure 2-7. Combination of a Drop
and a Horizontal Run
Figure 2-8. Combination of a
Rise, a Drop and a Horizontal Run
SV1196
SV1195
SV1194
Summary of Contents for QD0202A
Page 3: ......
Page 14: ...General Information Section 1 1 4 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 34: ...Installation Instructions Section 2 2 20 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...Maintenance Section 3 3 16 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 93: ...Section 6 Electrical System Part No 80 1100 3 6 37 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...Electrical System Section 6 6 56 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 135: ...Section 7 Refrigeration System Part No 80 1100 3 7 23 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 168: ...Refrigeration System Section 7 7 56 Part No 80 1100 3 Figure 7 18 Using Pinch Off Tool SV1406 ...
Page 174: ...Refrigeration System Section 7 7 62 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 175: ...Section 7 Refrigeration System Part No 80 1100 3 7 63 THIS PAGE INTENTIONALLY LEFT BLANK ...