Section 7
Refrigeration System
Part No. 80-1100-3
7-17
ANALYZING DISCHARGE PRESSURE
DURING FREEZE OR HARVEST CYCLE
Procedure
1. Determine the ice machine operating conditions:
Air temp. entering condenser
______
Air temp. around ice machine
______
Water temp. entering sump trough
______
2. Refer to Operating Pressure Chart for ice machine
being checked. (These charts begin on
Page 7-33
.)
Use the operating conditions determined in step 1 to
find the published normal discharge pressures.
Freeze Cycle _______
Harvest Cycle_______
3. Perform an actual discharge pressure check.
4. Compare the actual discharge pressure (step 3) with
the published discharge pressure (step 2).
The discharge pressure is normal when the actual
pressure falls within the published pressure range for the
ice machine’s operating conditions.
Freeze Cycle Discharge Pressure High Checklist
Freeze Cycle Discharge Pressure Low Checklist
NOTE: Do not limit your diagnosis to only the items listed in the checklists.
Freeze
Cycle PSIG
Harvest
Cycle PSIG
Beginning of Cycle
__________
__________
Middle of Cycle
__________
__________
End of Cycle
__________
__________
Possible Cause
Check/Correct
Improper installation
See “Installation/Visual Inspection Checklist” on
Page 7-10
Restricted condenser air flow (air-cooled models)
High inlet air temperature (110°F/43.3°C max.)
Condenser discharge air recirculation
Dirty condenser filter
Dirty condenser fins
Defective fan cycling control
Defective fan motor
Restricted condenser water flow (water-cooled
models)
Low water pressure (20 psi min.)
High inlet water temperature (90°F/32.2°C max.)
Dirty condenser
Dirty/defective water regulating valve
Water regulating valve out of adjustment
Improper refrigerant charge
Overcharged
Non-condensables in system
Wrong type of refrigerant
Other
Non-Manitowoc components in system
High side refrigerant lines/component restricted (before mid-condenser)
Defective head pressure control valve (remote models)
Possible Cause
Check/Correct
Improper installation
See “Installation/Visual Inspection Checklist” on
Page 7-10
Improper refrigerant charge
Undercharged
Wrong type of refrigerant
Water regulating valve (water-cooled condensers)
Out of adjustment
Defective
Other
Non-Manitowoc components in system
Defective head pressure control valve (remote models)
Defective fan cycle control
Summary of Contents for QD0202A
Page 3: ......
Page 14: ...General Information Section 1 1 4 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 34: ...Installation Instructions Section 2 2 20 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...Maintenance Section 3 3 16 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 93: ...Section 6 Electrical System Part No 80 1100 3 6 37 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...Electrical System Section 6 6 56 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 135: ...Section 7 Refrigeration System Part No 80 1100 3 7 23 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 168: ...Refrigeration System Section 7 7 56 Part No 80 1100 3 Figure 7 18 Using Pinch Off Tool SV1406 ...
Page 174: ...Refrigeration System Section 7 7 62 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 175: ...Section 7 Refrigeration System Part No 80 1100 3 7 63 THIS PAGE INTENTIONALLY LEFT BLANK ...