Refrigeration System
Section 7
7-38
Part No. 80-1100-3
Q450 SERIES
Remote
NOTE: These characteristics may vary depending on
operating conditions.
Cycle Times
Freeze Time + Harvest Time = Total Cycle Time
24 Hour Ice Production
Operating Pressures
Q600 SERIES
Self-Contained Air-Cooled
NOTE: These characteristics may vary depending on
operating conditions.
Cycle Times
Freeze Time + Harvest Time = Total Cycle Time
24 Hour Ice Production
Operating Pressures
Air Temp.
Entering
Condenser
°F/°C
Freeze Time
Harvest
Time
Water Temperature °F/°C
50/10.0
70/21.1
90/32.2
-20/-28.9 to
70/21.1
10.6-12.5
12.0-14.0
13.3-15.6
1-2.5
80/26.7
10.9-12.8
12.3-14.4
13.7-16.0
90/32.2
11.1-13.1
12.6-14.8
14.1-16.5
100/37.8
12.0-14.0
13.7-16.0
15.5-18.0
110/43.3
13.3-15.6
15.5-18.0
17.6-20.6
Times in minutes
Air Temp.
Entering
Condenser
°F/°C
Water Temperature °F/°C
50/10.0
70/21.1
90/32.2
-20/-28.9 to
70/21.1
490
440
400
80/26.7
480
430
390
90/32.2
470
420
380
100/37.8
440
390
350
110/43.3
400
350
310
Based on average ice slab weight of 4.12- 4.75lb
Regular cube derate is 7%
Ratings with JC0495 condenser, dice or half dice cubes
Air Temp.
Entering
Condenser
°F/°C
Freeze Cycle
Harvest Cycle
Discharg
e
Pressure
PSIG
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Suction
Pressure
PSIG
-20/-28.9 to
50/10.0
225-245
50-32
175-190
85-100
70/21.1
230-250
50-32
175-190
85-100
80/26.7
240-260
52-32
180-195
85-100
90/32.2
245-270
54-35
185-200
85-100
100/37.8
280-310
57-37
190-205
90-105
110/43.3
290-325
64-39
190-205
95-110
Suction pressure drops gradually throughout the freeze cycle
Air Temp.
Entering
Condenser
°F/°C
Freeze Time
Harvest
Time
Water Temperature °F/°C
50/10.0
70/21.1
90/32.2
70/21.1
7.1-8.4
7.8-9.2
8.6-10.1
1-2.5
80/26.7
7.8-9.2
8.6-10.1
9.5-11.2
90/32.2
8.6-10.1
9.5-11.2
10.4-12.2
100/37.8
9.5-11.2
10.6-12.5
12.0-14.0
Times in minutes
Air Temp.
Entering
Condenser
°F/°C
Water Temperature °F/°C
50/10.0
70/21.1
90/32.2
70/21.1
690
640
590
80/26.7
640
590
540
90/32.2
590
540
500
100/37.8
540
490
440
Based on average ice slab weight of 4.12- 4.75lb
Regular cube derate is 7%
Air Temp.
Entering
Condenser
°F/°C
Freeze Cycle
Harvest Cycle
Discharg
e
Pressure
PSIG
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Suction
Pressure
PSIG
50/10.0
195-260
42-22
155-180
75-95
70/21.1
220-290
44-22
160-185
85-100
80/26.7
220-305
52-22
160-190
90-110
90/32.2
250-325
52-23
175-195
95-115
100/37.8
280-355
54-30
195-210
95-125
110/43.3
300-385
56-32
200-225
100-135
Suction pressure drops gradually throughout the freeze cycle
Summary of Contents for QD0202A
Page 3: ......
Page 14: ...General Information Section 1 1 4 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 34: ...Installation Instructions Section 2 2 20 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...Maintenance Section 3 3 16 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 93: ...Section 6 Electrical System Part No 80 1100 3 6 37 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...Electrical System Section 6 6 56 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 135: ...Section 7 Refrigeration System Part No 80 1100 3 7 23 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 168: ...Refrigeration System Section 7 7 56 Part No 80 1100 3 Figure 7 18 Using Pinch Off Tool SV1406 ...
Page 174: ...Refrigeration System Section 7 7 62 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 175: ...Section 7 Refrigeration System Part No 80 1100 3 7 63 THIS PAGE INTENTIONALLY LEFT BLANK ...