104
Part Number STH025 02/12
REMOTE CONDENSER
Single Evaporator Models
NOTE:
The power button must be depressed and the
water curtain/ice dampers must be in place on the
evaporator before the ice machine will start.
Initial Start-Up or Start-Up After
Automatic Shut-Off
1. Water Purge
Before the compressor starts, the water pump and
water dump solenoid are energized for 45 seconds, to
completely purge the ice machine of old water. This
feature ensures that the ice making cycle starts with
fresh water.
2. Refrigeration System Start-Up
The harvest valve, air pump and harvest pressure
regulating (HPR) solenoid valves energize to equalize
high and low side refrigeration pressure.
After 5 seconds the liquid line solenoid valve
energizes and the contactor energizes the compressor
and condenser fan motor.
Freeze Sequence
3. Prechill
The compressor is on for 30 seconds (60 seconds
initial cycle) prior to water flow, to prechill the
evaporator. The water fill valve is also energized and
will remain on until water completes the water level
probe circuit.
4. Freeze
The water pump(s) energizes and water flows over the
evaporator. After water contacts the water level probe
the water fill valve de-energizes. The control board will
automatically cycle the water fill valve within the 6
minute water fill time limit. The valve energizes once in
the pre-chill and up to twice in the freeze cycle.
The freeze cycle continues until the six minute freeze
lock expires and enough ice has formed to send a
signal from the ice thickness probe to the control
board.
Summary of Contents for Indigo Series
Page 2: ......
Page 22: ...22 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 33: ...Part Number STH025 02 12 33 This Page Intentionally Left Blank ...
Page 34: ...34 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 54: ...54 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 55: ...Part Number STH025 02 12 55 This Page Intentionally Left Blank ...
Page 56: ...56 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 108: ...108 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 113: ...Part Number STH025 02 12 113 This Page Intentionally Left Blank ...
Page 114: ...114 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 121: ...Part Number STH025 02 12 121 This Page Intentionally Left Blank ...
Page 122: ...122 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 154: ...154 Is the evaporator dirty Dry evaporator first then check YES NO NO ...
Page 155: ...Part Number STH025 02 12 155 This Page Intentionally Left Blank ...
Page 156: ...156 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 161: ...Part Number STH025 02 12 161 This Page Intentionally Left Blank ...
Page 197: ...Part Number STH025 02 12 197 This Page Intentionally Left Blank ...
Page 213: ...Part Number STH025 02 12 213 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 222: ...222 ...
Page 254: ...254 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 256: ...256 Part Number STH025 02 12 I0300 I0450 I0500 I0520 Self Contained Air Water cooled 1 Ph ...
Page 257: ...Part Number STH025 02 12 257 I0320 Self Contained Air Water cooled 1 Ph ...
Page 258: ...258 Part Number STH025 02 12 I0500 Remote Air cooled 1Ph ...
Page 259: ...Part Number STH025 02 12 259 I0600 I0850 I1000 I1200 Self Contained Air Water cooled 1 3 Ph ...
Page 260: ...260 Part Number STH025 02 12 I0600 I0850 I1000 Remote Condenser Air cooled 1 3 Ph ...
Page 261: ...Part Number STH025 02 12 261 I1400 I1800 Self Contained Air Water cooled 1 3 Ph ...
Page 262: ...262 Part Number STH025 02 12 I1400 I1800 Remote Air cooled 1 3 Ph ...
Page 266: ...266 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 267: ...Part Number STH025 02 12 267 This Page Intentionally Left Blank ...
Page 268: ...268 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 269: ......