Part Number STH025 02/12
PTCR Operation Check
1. Visually inspect the PTCR. Check for signs of
physical damage.
NOTE:
The PTCR case temperature may reach
210°F (100°C) while the compressor is running. This is
normal. Do not change a PTCR just because it is hot.
2. Wait at least 10 minutes for the PTCR to cool to
room temperature.
3. Remove the PTCR from the ice machine.
4. Measure the resistance of the PTCR as shown.
The resistance reading must be between:
•
Two Terminal PTCR =18 to 40 ohms
•
Three Terminal PTCR =
8 to 22 ohms.
Three Terminal PTCR
Measure Resistance At Ends
Two Terminal PTCR
Leave Jumper Wire Attached
Measure Resistance @ Center and End
Summary of Contents for Indigo Series
Page 2: ......
Page 22: ...22 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 33: ...Part Number STH025 02 12 33 This Page Intentionally Left Blank ...
Page 34: ...34 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 54: ...54 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 55: ...Part Number STH025 02 12 55 This Page Intentionally Left Blank ...
Page 56: ...56 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 108: ...108 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 113: ...Part Number STH025 02 12 113 This Page Intentionally Left Blank ...
Page 114: ...114 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 121: ...Part Number STH025 02 12 121 This Page Intentionally Left Blank ...
Page 122: ...122 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 154: ...154 Is the evaporator dirty Dry evaporator first then check YES NO NO ...
Page 155: ...Part Number STH025 02 12 155 This Page Intentionally Left Blank ...
Page 156: ...156 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 161: ...Part Number STH025 02 12 161 This Page Intentionally Left Blank ...
Page 197: ...Part Number STH025 02 12 197 This Page Intentionally Left Blank ...
Page 213: ...Part Number STH025 02 12 213 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 222: ...222 ...
Page 254: ...254 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 256: ...256 Part Number STH025 02 12 I0300 I0450 I0500 I0520 Self Contained Air Water cooled 1 Ph ...
Page 257: ...Part Number STH025 02 12 257 I0320 Self Contained Air Water cooled 1 Ph ...
Page 258: ...258 Part Number STH025 02 12 I0500 Remote Air cooled 1Ph ...
Page 259: ...Part Number STH025 02 12 259 I0600 I0850 I1000 I1200 Self Contained Air Water cooled 1 3 Ph ...
Page 260: ...260 Part Number STH025 02 12 I0600 I0850 I1000 Remote Condenser Air cooled 1 3 Ph ...
Page 261: ...Part Number STH025 02 12 261 I1400 I1800 Self Contained Air Water cooled 1 3 Ph ...
Page 262: ...262 Part Number STH025 02 12 I1400 I1800 Remote Air cooled 1 3 Ph ...
Page 266: ...266 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 267: ...Part Number STH025 02 12 267 This Page Intentionally Left Blank ...
Page 268: ...268 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 269: ......