216
Part Number STH025 02/12
System Contamination Clean-Up
General
This section describes the basic requirements for
restoring contaminated systems to reliable service.
DETERMINING SEVERITY OF CONTAMINATION
System contamination is generally caused by either
moisture or residue from compressor burnout entering
the refrigeration system.
Inspection of the refrigerant usually provides the first
indication of system contamination. Obvious moisture
or an acrid odor in the refrigerant indicates
contamination.
If either condition is found, or if contamination is
suspected, use a Total Test Kit from Totaline or a
similar diagnostic tool. These devices sample
refrigerant, eliminating the need to take an oil sample.
Follow the manufacturer’s directions.
If a refrigerant test kit indicates harmful levels of
contamination, or if a test kit is not available, inspect
the compressor oil.
1. Remove the refrigerant charge from the ice
machine.
2. Remove the compressor from the system.
3. Check the odor and appearance of the oil.
4. Inspect open suction and discharge lines at the
compressor for burnout deposits.
5. If no signs of contamination are present, perform
an acid oil test.
Check the chart on the next page to determine the
type of cleanup required.
Important
Manitowoc Ice assumes no responsibility for the use
of contaminated refrigerant. Damage resulting from
the use of contaminated refrigerant is the sole
responsibility of the servicing company.
Summary of Contents for Indigo Series
Page 2: ......
Page 22: ...22 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 33: ...Part Number STH025 02 12 33 This Page Intentionally Left Blank ...
Page 34: ...34 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 54: ...54 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 55: ...Part Number STH025 02 12 55 This Page Intentionally Left Blank ...
Page 56: ...56 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 108: ...108 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 113: ...Part Number STH025 02 12 113 This Page Intentionally Left Blank ...
Page 114: ...114 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 121: ...Part Number STH025 02 12 121 This Page Intentionally Left Blank ...
Page 122: ...122 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 154: ...154 Is the evaporator dirty Dry evaporator first then check YES NO NO ...
Page 155: ...Part Number STH025 02 12 155 This Page Intentionally Left Blank ...
Page 156: ...156 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 161: ...Part Number STH025 02 12 161 This Page Intentionally Left Blank ...
Page 197: ...Part Number STH025 02 12 197 This Page Intentionally Left Blank ...
Page 213: ...Part Number STH025 02 12 213 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 222: ...222 ...
Page 254: ...254 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 256: ...256 Part Number STH025 02 12 I0300 I0450 I0500 I0520 Self Contained Air Water cooled 1 Ph ...
Page 257: ...Part Number STH025 02 12 257 I0320 Self Contained Air Water cooled 1 Ph ...
Page 258: ...258 Part Number STH025 02 12 I0500 Remote Air cooled 1Ph ...
Page 259: ...Part Number STH025 02 12 259 I0600 I0850 I1000 I1200 Self Contained Air Water cooled 1 3 Ph ...
Page 260: ...260 Part Number STH025 02 12 I0600 I0850 I1000 Remote Condenser Air cooled 1 3 Ph ...
Page 261: ...Part Number STH025 02 12 261 I1400 I1800 Self Contained Air Water cooled 1 3 Ph ...
Page 262: ...262 Part Number STH025 02 12 I1400 I1800 Remote Air cooled 1 3 Ph ...
Page 266: ...266 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 267: ...Part Number STH025 02 12 267 This Page Intentionally Left Blank ...
Page 268: ...268 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 269: ......