FREEZE CYCLE
The HPR system is not used during the freeze cycle.
The HPR solenoid is closed (de-energized),
preventing refrigerant flow into the HPR valve.
HARVEST CYCLE
During the harvest cycle, the check valve in the
discharge line prevents refrigerant in the remote
condenser and receiver from back feeding into the
evaporator and condensing to liquid.
The HPR solenoid is opened (energized) during the
harvest cycle, allowing refrigerant gas from the top of
the receiver to flow into the HPR valve. The HPR valve
modulates open and closed, raising the suction
pressure high enough to sustain heat for the harvest
cycle, without allowing refrigerant to condense to liquid
in the evaporator.
In general, harvest cycle suction pressure rises, then
stabilizes in the range of 70-100 psig (517-758 kPa).
Exact pressures vary from model to model. Refer to
cycle time/24 hour ice production and operational
pressure charts.
HPR DIAGNOSTICS
Steps 1 through 4 can be quickly verified without
attaching a manifold gauge set or thermometer.
All questions must have a yes answer to continue
the diagnostic procedure.
1. Liquid line warm?
(Body temperature is normal)
If liquid line is cooler than body temperature, refer
to head pressure control valve diagnostics
page 198.
2. Ice fill pattern normal?
Refer to “Ice Formation Pattern” if ice fill is not
normal page 133.
Summary of Contents for Indigo Series
Page 2: ......
Page 22: ...22 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 33: ...Part Number STH025 02 12 33 This Page Intentionally Left Blank ...
Page 34: ...34 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 54: ...54 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 55: ...Part Number STH025 02 12 55 This Page Intentionally Left Blank ...
Page 56: ...56 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 108: ...108 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 113: ...Part Number STH025 02 12 113 This Page Intentionally Left Blank ...
Page 114: ...114 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 121: ...Part Number STH025 02 12 121 This Page Intentionally Left Blank ...
Page 122: ...122 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 154: ...154 Is the evaporator dirty Dry evaporator first then check YES NO NO ...
Page 155: ...Part Number STH025 02 12 155 This Page Intentionally Left Blank ...
Page 156: ...156 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 161: ...Part Number STH025 02 12 161 This Page Intentionally Left Blank ...
Page 197: ...Part Number STH025 02 12 197 This Page Intentionally Left Blank ...
Page 213: ...Part Number STH025 02 12 213 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 222: ...222 ...
Page 254: ...254 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 256: ...256 Part Number STH025 02 12 I0300 I0450 I0500 I0520 Self Contained Air Water cooled 1 Ph ...
Page 257: ...Part Number STH025 02 12 257 I0320 Self Contained Air Water cooled 1 Ph ...
Page 258: ...258 Part Number STH025 02 12 I0500 Remote Air cooled 1Ph ...
Page 259: ...Part Number STH025 02 12 259 I0600 I0850 I1000 I1200 Self Contained Air Water cooled 1 3 Ph ...
Page 260: ...260 Part Number STH025 02 12 I0600 I0850 I1000 Remote Condenser Air cooled 1 3 Ph ...
Page 261: ...Part Number STH025 02 12 261 I1400 I1800 Self Contained Air Water cooled 1 3 Ph ...
Page 262: ...262 Part Number STH025 02 12 I1400 I1800 Remote Air cooled 1 3 Ph ...
Page 266: ...266 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 267: ...Part Number STH025 02 12 267 This Page Intentionally Left Blank ...
Page 268: ...268 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 269: ......