204
Part Number STH025 02/12
3. Freeze time normal?
(Refer to Cycle Times/Refrigerant Pressures/24
Hour Ice Production Charts page 225)
Shorter freeze cycles
- Refer to head pressure
control valve diagnostics page 198.
Longer freeze cycles
- Refer to water system
checklist page 132, then refer to Refrigeration
Diagnostic Procedures.
4. Harvest time is longer than normal and control
board indicates safety limit #2?
(Refer to Cycle Times/Refrigerant Pressures/24
Hour Ice Production Charts page 225)
Connect refrigeration manifold gauge set to the
access valves on the front of the ice machine.
Establish baseline by recording suction and
discharge pressure and freeze & harvest cycle
times. (Refer to “
Freeze Cycle Refrigeration
System Operational Analysis Tables
” for data
collection detail page 123).
5. Discharge line temperature is greater than 150°F
(66°C) [I0850/I1000 Air/Water Only -
140°F (60°C)] at the end of the freeze cycle? (See
Discharge Line Temperature Analysis on
page 144)
6. Freeze cycle Head Pressure is in the range
indicated in the cycle time/24 hour ice production
and operational pressure chart?
If the head pressure is low refer to head pressure
control valve diagnostics page 198.
7. Freeze cycle Suction Pressure normal?
Refer to analyzing suction pressure if suction
pressure is high or low page 138.
8. Harvest cycle suction and discharge pressures
are lower than indicated in the cycle times/
refrigerant pressures/24 hour ice production
chart?
9. Replace Harvest Pressure Regulating solenoid.
Summary of Contents for Indigo Series
Page 2: ......
Page 22: ...22 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 33: ...Part Number STH025 02 12 33 This Page Intentionally Left Blank ...
Page 34: ...34 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 54: ...54 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 55: ...Part Number STH025 02 12 55 This Page Intentionally Left Blank ...
Page 56: ...56 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 108: ...108 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 113: ...Part Number STH025 02 12 113 This Page Intentionally Left Blank ...
Page 114: ...114 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 121: ...Part Number STH025 02 12 121 This Page Intentionally Left Blank ...
Page 122: ...122 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 154: ...154 Is the evaporator dirty Dry evaporator first then check YES NO NO ...
Page 155: ...Part Number STH025 02 12 155 This Page Intentionally Left Blank ...
Page 156: ...156 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 161: ...Part Number STH025 02 12 161 This Page Intentionally Left Blank ...
Page 197: ...Part Number STH025 02 12 197 This Page Intentionally Left Blank ...
Page 213: ...Part Number STH025 02 12 213 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 222: ...222 ...
Page 254: ...254 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 256: ...256 Part Number STH025 02 12 I0300 I0450 I0500 I0520 Self Contained Air Water cooled 1 Ph ...
Page 257: ...Part Number STH025 02 12 257 I0320 Self Contained Air Water cooled 1 Ph ...
Page 258: ...258 Part Number STH025 02 12 I0500 Remote Air cooled 1Ph ...
Page 259: ...Part Number STH025 02 12 259 I0600 I0850 I1000 I1200 Self Contained Air Water cooled 1 3 Ph ...
Page 260: ...260 Part Number STH025 02 12 I0600 I0850 I1000 Remote Condenser Air cooled 1 3 Ph ...
Page 261: ...Part Number STH025 02 12 261 I1400 I1800 Self Contained Air Water cooled 1 3 Ph ...
Page 262: ...262 Part Number STH025 02 12 I1400 I1800 Remote Air cooled 1 3 Ph ...
Page 266: ...266 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 267: ...Part Number STH025 02 12 267 This Page Intentionally Left Blank ...
Page 268: ...268 Part Number STH025 02 12 This Page Intentionally Left Blank ...
Page 269: ......