Part Number Preliminary 6/11
Calculated Line Set Distance
The maximum calculated distance is 150' (45.7 m).
Line set rises, drops, horizontal runs (or combinations
of these) in excess of the stated maximums will
exceed compressor start-up and design limits. This will
cause poor oil return to the compressor.
Make the following calculations to make sure the line
set layout is within specifications.
1. Insert the
measured rise
into the formula below.
Multiply by 1.7 to get the
calculated rise.
(Example: A condenser located 10 feet above the
ice machine has a
calculated rise
of 17 feet.)
2. Insert the
measured drop
into the formula below.
Multiply by 6.6 to get the
calculated drop.
(Example. A condenser located 10 feet below the
ice machine has a
calculated drop
of 66 feet.)
3. Insert the
measured horizontal distance
into the
formula below. No calculation is necessary.
4. Add together the
calculated rise, calculated
drop,
and
horizontal distance
to get the
total
calculated distance.
If this total exceeds 150'
(45.7 m), move the condenser to a new location
and perform the calculations again.
Maximum Line Set Distance Formula
Step 1
Measured Rise ____ X 1.7 = ______Calculated Rise
(35 ft. Max)
Step 2
Measured Drop ____ X 6.6 = ______Calculated Drop
(15 ft. Max.)
Step 3
Measured Horizontal Distance = _________Horizontal
(100 ft. Max.) Distance
Step 4
Total Calculated Distance = ________Total Calculated
(150 ft. Max.) Distance
Summary of Contents for ICVD3095
Page 2: ......
Page 12: ...12 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 25: ...Part Number Preliminary 6 11 25 This Page Intentionally Left Blank ...
Page 26: ...26 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 72: ...72 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 101: ...Part Number Preliminary 6 11 101 This Page Intentionally Left Blank ...
Page 132: ...132 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 137: ...Part Number Preliminary 6 11 137 This Page Intentionally Left Blank ...
Page 138: ...138 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 187: ...Part Number Preliminary 6 11 187 This Page Intentionally Left Blank ...
Page 188: ...188 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 225: ...Part Number Preliminary 6 11 225 This Page Intentionally Left Blank ...
Page 226: ...226 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 262: ...262 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 283: ...Part Number Preliminary 6 11 283 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 291: ...Part Number Preliminary 6 11 291 This Page Intentionally Left Blank ...
Page 298: ...298 Part Number Preliminary 6 11 USING PINCH OFF TOOL ...
Page 303: ...Part Number Preliminary 6 11 303 This Page Intentionally Left Blank ...
Page 304: ...304 Part Number Preliminary 6 11 ...
Page 305: ...Part Number Preliminary 6 11 305 This Page Intentionally Left Blank ...
Page 306: ...306 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 337: ...Part Number Preliminary 6 11 337 I0500 Remote Air cooled 1Ph ...
Page 339: ...Part Number Preliminary 6 11 339 I0600 I0850 I1000 Remote Condenser Air cooled 1 3 Ph ...
Page 341: ...Part Number Preliminary 6 11 341 IB0690C IB0890C IB1090C QuietQube Remote Air cooled 1 3 Ph ...
Page 342: ...342 Part Number Preliminary 6 11 I1400 I1800 Self Contained Air Water cooled 1 3 Ph ...
Page 343: ...Part Number Preliminary 6 11 343 I1400 I1800 Remote Air cooled 1 3 Ph ...
Page 349: ......