Part Number Preliminary 6/11
QuietQube® Models - Harvest Valve Analysis
Symptoms of a harvest valve remaining partially open
during the freeze cycle can be similar to symptoms of
either an expansion valve or compressor problem. The
best way to diagnose a harvest valve is by using
Manitowoc’s Ice Machine Freeze Cycle Refrigeration
System Operational Analysis Table.
Use the following procedures to determine if a harvest
valve is remaining partially open during the freeze
cycle.
QUIETQUBE® REMOTE CONDENSING UNIT
MODELS HARVEST VALVE ANALYSIS
The valve can fail in two positions:
•
Valve will not open in the Harvest cycle.
•
Valve remains open during the Freeze cycle.
Valve will not open in the Harvest cycle
Although the circuit board has initiated a Harvest
cycle, suction and discharge pressures remain
unchanged from the Freeze cycle. The ice machine
will remain in the Harvest cycle for 3.5 minutes (7
minutes Quad Evaporators), then initiate a new
Freeze cycle.
Valve remains open in the Freeze cycle
Symptoms of a harvest valve remaining partially open
during the Freeze cycle can be similar to symptoms of
an expansion valve, float valve or compressor
problem. Symptoms are dependent on the amount of
leakage in the Freeze cycle.
A small amount of leakage will cause increased freeze
times and an ice fill pattern that is normal.
As the amount of leakage increases, the length of the
Freeze cycle increases and the amount of ice on the
bottom of the evaporator decreases.
A small amount of leakage will cause an audible
indication as the vapor passes through the valve. As
the size of the leak increases, the audible indication
becomes more apparent.
Summary of Contents for ICVD3095
Page 2: ......
Page 12: ...12 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 25: ...Part Number Preliminary 6 11 25 This Page Intentionally Left Blank ...
Page 26: ...26 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 72: ...72 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 101: ...Part Number Preliminary 6 11 101 This Page Intentionally Left Blank ...
Page 132: ...132 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 137: ...Part Number Preliminary 6 11 137 This Page Intentionally Left Blank ...
Page 138: ...138 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 187: ...Part Number Preliminary 6 11 187 This Page Intentionally Left Blank ...
Page 188: ...188 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 225: ...Part Number Preliminary 6 11 225 This Page Intentionally Left Blank ...
Page 226: ...226 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 262: ...262 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 283: ...Part Number Preliminary 6 11 283 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 291: ...Part Number Preliminary 6 11 291 This Page Intentionally Left Blank ...
Page 298: ...298 Part Number Preliminary 6 11 USING PINCH OFF TOOL ...
Page 303: ...Part Number Preliminary 6 11 303 This Page Intentionally Left Blank ...
Page 304: ...304 Part Number Preliminary 6 11 ...
Page 305: ...Part Number Preliminary 6 11 305 This Page Intentionally Left Blank ...
Page 306: ...306 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Page 337: ...Part Number Preliminary 6 11 337 I0500 Remote Air cooled 1Ph ...
Page 339: ...Part Number Preliminary 6 11 339 I0600 I0850 I1000 Remote Condenser Air cooled 1 3 Ph ...
Page 341: ...Part Number Preliminary 6 11 341 IB0690C IB0890C IB1090C QuietQube Remote Air cooled 1 3 Ph ...
Page 342: ...342 Part Number Preliminary 6 11 I1400 I1800 Self Contained Air Water cooled 1 3 Ph ...
Page 343: ...Part Number Preliminary 6 11 343 I1400 I1800 Remote Air cooled 1 3 Ph ...
Page 349: ......