TPM 083/12
8
Park Allé 366, DK-2605 Brondby
Telefon 70 20 19 11; E-mail:[email protected]
5. Statement of installations
5.1.
Statement of installations
Tab. 5.1.1. Statement of installations
Damper
size
FDMC installation
Classifi-
cation
Figure
100-400
Damper installed on a solid wall construction. Space between damper and
wall is filled by mortar, gypsum or another approved fire sealing system
for damper installation.
EIS 60
7
Damper installed on a gypsum wall construction. Space between damper
and wall is filled by mortar, gypsum or another approved fire sealing
system for damper installation.
EIS 60
8
Damper installed on a solid ceiling construction. Space between damper
and ceiling is filled by mortar, gypsum or another approved fire sealing
system for damper installation.
EIS 60
9
Duct ended by installation shaft. Space between damper and ceiling is
filled by mortar, gypsum or another approved fire sealing system for
damper installation - solid wall construction
EIS 60
10
Duct ended by installation shaft. Space between damper and ceiling is
filled by mortar, gypsum or another approved fire sealing system for
damper installation - gypsum wall construction
EIS 60
11
Fig. 7
Installation on a solid wall construction
Position:
1
Fire damper FDMC
2
Mortar or gypsum with min. density 800 kg/m
3
or another approved fire
sealing system for damper installation
2
1
2
1