Fig. 13 Actuating mechanism BELIMO BLF 24-T-ST
9. Electrical Components, Connection Diagrams
9.1.
Actuating
mechanism
Tab. 9.1.1. Actuating mechanism BELIMO BLF 24-T-ST (24-ST)
Servopohon BELIMO
BLF 24-T-ST(24-ST)
Nominal voltage
AC 24V 50/60Hz
DC 24 V
Power consumption - motoring
-
holding
5 W
2,5 W
Dimensioning
7 VA (Imax 5,8 A @ 5 ms)
Protection Class
III
Degree of protection
IP 54
Running time - motor
-
spring
return
40..75 s
~ 20 s
Ambient Temperature - normal duty
- safety duty
-
non-operating
temperature
- 30 °C … + 50 °C
The safe position will be attained up to max. 75°C
- 40 °C … + 50 °C
Connecting - motor
-
auxiliary
switch
cable 1 m, 2 x 0,75 mm
2
with 3 pole plug
cable 1 m, 6 x 0,75 mm
2
with 6 pole plug
Thermal trips*
Tf1: duct outside temperature 72°C
Tf2/Tf3: duct inside temperature 72°C
* only BLF 24-T-ST