background image

TPM 083/12

3

Park Allé 366, DK-2605 Brondby
Telefon 70 20 19 11; E-mail:[email protected]

II. GENERAL INFORMATION

1. Description

1.1. 

 

Fire dampers are shutters in piping systems of air-conditioning devices that prevent spreading
the fire and combustion products from one fire segment to the other one by means of closing the
air piping in the points of fire separating constructions.

1.4. 

 

The damper is sealed with a silicon packing against smoke penetration after closing the blade. At
the same time, the damper blade is bed in a material which enlarges its capacity and air proofs
the air duct.

1.3. 

 

Dampers blade automatically closes air duct using an actuating mechanism back spring. The
back spring of the actuating mechanism is started when the thermoelectrical starting mechanism
BAE 72B-S is activated, when a reset button on BAE 72B-S is pushed or when a power supply
of the actuating mechanism is stopped (for FDMC-SRD only when the power supply of the
actuating mechanism is stopped).

1.2. 

 

Dampers are in all variants classified as EI 60 ve, ho (i   o) S acc. EN 13501-3 and tested acc.
EN 1366-2.

1.5. 

 

Dampers have one inspection hole, since the shutting device and the inspection hole can be set
into the most advantageous position (with respect to the operation and manipulation with the
control device).

1.6. 

 

Exact damper function is provided under the following conditions:

 

  

a) Maximum air circulation speed: 12 m.s

-1

 

  

Maximum pressure difference: 1200 Pa

 

  

b) Dampers could be displaced into position “CLOSED” only in case that ventilator, or Air

  

  Handling Unit is switched off. The goal is the securing of proper closing and safe

  

  function of Fire Damper in case of Fire.

 

  

 

  

c) The air circulation in the whole damper section must be secured as steady on whole

   

surface.

1.7. 

 

Dampers are designed for macroclimatic areas with mild climate according to EN 60 721-3-3.

1.8. 

 

Dampers are suitable for systems without abrasive, chemical and adhesive particles.

1.9. 

 

Temperature in the place of installation is permitted to range from - 20°C to + 50°C.

1.11. 

 

In this document are used next signs and units.

Key :

w

[m.s

-1

]

air velocity

  p

[Pa]

pressure loss

L

w

[dB]

level of acoustic output

[ ]

pressure loss coefficient

[kg.m

-3

]

density

A,B, a, c, 
e, f

[mm]

dimension

S [m

2

]

area

1.10. 

 

If is not noticed other way, all dimensions and weight are in millimeters and kilograms.

Summary of Contents for FDMC

Page 1: ...FDMC FDMC SRD TPM 083 12 DK VALID FROM 15 1 2012 FIRE DAMPER AND FIRE DAMPER SMOKE RELIEF...

Page 2: ...ription 3 2 Design 4 3 Dimensions weights 5 4 Placement and Assembly 6 5 Statement of installations 8 III TECHNICAL DATA 9 6 Pressure loss 9 7 Coefficient of local pressure loss 10 8 Noise data 10 9 E...

Page 3: ...N 13501 3 and tested acc EN 1366 2 1 5 Dampers have one inspection hole since the shutting device and the inspection hole can be set into the most advantageous position with respect to the operation a...

Page 4: ...of the actuating mechanism These fuses are activated when temperature 72 C has been exceeded the fuse Tf1 when the temperature around the damper and the fuses Tf2 Tf3 when the temperature inside the...

Page 5: ...1 E mail oeland oeland dk Position 1 Damper body 4 BAE 72B S thermoelectrical starting mechanism 2 Damper blade 5 Inspection hole covering 3 Actuating mechanism Fig 2 Fire damper FDMC Fig 3 Fire dampe...

Page 6: ...a 4 Placement and Assembly 4 1 Fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages of fire separating constructions Damper assembly procedures must be...

Page 7: ...mper body during opening or closing 4 7 Installation opening dimensions 4 2 To provide needed access space to the control device all other objects must be situated at least 350 mm from the control par...

Page 8: ...tallation EIS 60 8 Damper installed on a solid ceiling construction Space between damper and ceiling is filled by mortar gypsum or another approved fire sealing system for damper installation EIS 60 9...

Page 9: ...min density 800 kg m3 or another approved fire sealing system for damper installation Fig 8 Installation on a gypsum wall construction 2 1 2 1 Fig 9 Installation on a ceiling wall construction 1 2 2 1...

Page 10: ...t solid wall construction 4 Position 1 Fire damper FDMC 3 Duct 2 Mortar or gypsum with min density 800 kg m3 or another approved fire sealing system for damper installation 4 Installation shaft 3 1 2...

Page 11: ...oss for the nominal damper section see Tab 7 1 1 III TECHNICAL DATA 6 2 Determination of pressure loss by using diagram 6 2 1 1 2 kg m 3 Diagram 6 2 1 Pressure losses for air density 1 2 kg m 3 7 1 Co...

Page 12: ...see Tab 8 3 3 LWoct LW1 10 log S Lrel 8 3 Table of acoustics values Tab 8 3 1 Level of acoustic output LW1 related to the 1 m2 section w m s 1 0 1 0 2 0 3 0 4 0 6 0 8 1 1 5 2 2 5 3 3 5 2 9 0 11 5 14 7...

Page 13: ...l 48 8 10 log 0 0374 11 5 23 1 dB Tab 8 3 2 Correction to the weight filter A w m s 1 2 3 4 5 6 7 8 9 10 11 12 KA dB 15 0 11 8 9 8 8 4 7 3 6 4 5 7 5 0 4 5 4 0 3 6 Tab 8 3 3 Relative level expressing t...

Page 14: ...oring holding 5 W 2 5 W Dimensioning 7 VA Imax 5 8 A 5 ms Protection Class III Degree of protection IP 54 Running time motor spring return 40 75 s 20 s Ambient Temperature normal duty safety duty non...

Page 15: ...e fire damper function it is necessary to avoid blocking the closing mechanism and contact surfaces with collected dust fibre and sticky materials and solvents 13 Logistic terms 13 1 Dampers are trans...

Page 16: ...ile he is obliged to provide the fire protection another appropriate way 15 2 Before entering the dampers into operation after their assembly and by sequential checks the following checks must be carr...

Reviews: